C h a p t e r 2
Specifications
1. General Specifications
4. Cable Diagrams
2. Functional Specifications
5. Names and Functions of FP Parts
3. Interface Specifications
6. Flat Panel (FP) Dimensions
FP2600-T11 User Manual
2-1-2 Environment Specifications
2-1
*1
(See the next page's note)
2-1 General Specifications
(For AC100V)
2-1-1 Electrical Specifications
AC
100V
(FP2600-T11)
Operating T emperature
0
o
C to 50
o
C
Storage T emperature
-10
o
C to 60
o
C
Humidity
30 to 85%RH (non-condensing)
Vibration Endurance
19.8m/s
2
- 10 to 25 Hz (X,Y,Z directions - 30 minutes each)
Noise Immunity
Noise voltage: 1200 Vp-p
Pulse length: 1
µ
s
Rise time (rise/fall): 1 ns
Pollution Level
Not immune to corrosive gas
Grounding
Less than 100
Ω
, or your country's applicable standard
Protection*1
Equivalent to IP65f (JEM1030)
AC100V (FP2600-T11)
Rated Voltage
AC 85V to AC 132V 50/60Hz
Power Consumption
50VA or less
Allowable Voltage Drop
20ms or less
Voltage Endurance
AC1500V 20mA 1minute
(between the live wire and grounding terminals)
Insulation Resistance
DC500V -above 10M
Ω
(between the live wire and grounding terminals)