-13-
Menu/Ok
Q9
C
QA
Q4
Wiring
6
Wiring
• Strip the wire’s plastic covering to expose approximately
6.8mm of wire.
• When using a lay wire, Pro-face recommends you install a
blade-type or pin-type terminal connector.
• The torque required to secure a wire to a terminal is 0.5 N•m.
Power and voltage specifications may vary depending on your PRO-iO2
module’s model. Be sure to carefully read this Installation Guide and the
PRO-iO2 User Manual before turning the module’s power ON.
CAUTION
The following types of wires can be used:
*1 When operating devices with inductance loads, such as magnets and valves, Pro-face
recommends you use a diode, surge killer or varistor.
DC Power Module (DR*-****BD)
(1) 1A Fuse
(Fast-break type)
(2) Fuse (Up to 16A)
or circuit breaker
(3) Load
*1
24VCD
24VAC to 250VAC
50/60 Hz
or 5VDC to 30VDC
24VAC to 250VAC
50/60 Hz
5VDC to 30VDC
5VDC to 30VDC
24VAC to 250VAC
50/60 Hz
Wire Type
Lay wire
mm
2
0.25 to 2.5
0.25 to 0.75
0.2 to 2.5
0.2 to 2.5
0.2 to 1.5
AWG
*1
24 to 14
24 to 18
25 to 14
25 to 14
25 to 16
Simple Wires
Pin-type Terminal
*1 AWG stands for “American Wire Gauge” and indicates conductor thickness.