SPECIFICATIONS
INPUT TYPE
4-20 mA signal.
INPUT IMPEDANCE
100 ohms.
INPUT RESOLUTION
12 - bits, 0.1% of full scale.
SAMPLING CYCLE TIME
100 mS.
AVERAGING
8 consecutive samples.
ACCURACY
0.5% of full scale.
EXCITATION VOLTAGE
24 VDC, 30 mA available for loop powered transducers.
RELAY OUTPUTS
Four programmable relay outputs with LED indication. “Form C” (SPDT)
contacts: rated at 10A at 240 VAC.
LEVEL DISPLAY
Eight character alpha-numeric LED for process value and program parameters.
POWER
24 VDC (+/- 10%). 200 mA nominal, 400 mA max.
OPERATING TEMPERATURE
-15oC to 70oC (0oF to 150oF) at up to 0-90% RH non-condensing.
ENCLOSURE RATING
Front Panel:
IEC Standard IP54 (with additional gasket) for indoor use.
Rear Case:
IEC Standard IP20.
BAR GRAPH
20 segment bar graph display for process value. Each bar represents 5% of full scale.