4. PUMP STATUS CONNECTIONS
Dry contacts: use potential free contacts only for pump status inputs.
WARNING
Equipment damage will result if any voltage is connected to the input terminals.
5. OUTPUT RELAY CONNECTIONS
The relay outputs are rated up to 10 A (resistive) at 240 VAC, fuse protection is required indi-
vidually or as a group.
Motor starters
auxiliary contacts
Thermal switches
in motor winding.
Normally closed:
open on
over temperature.
Seal fail contact from
seal fail module.*
Do not connect if mois-
ture sensing probe is not
available in the pump.
*Seal fail module must be approved by pump manufacturer.
FIGURE 4 Pump Status connections.
FIGURE 5 Typical Output Relay connections.
PRIMEX ™ 10 SP6R-LSC Level Controller User Manual