HI ALARM
AUTO RST / MANUAL
AUTO RST:
The high level alarm is automatically cleared as the
level drops below the HI ALARM set point.
MANUAL:
The alarm will remain on until the RESET button is
pressed by the operator.
LO
ALARM
AUTO RST / MANUAL
AUTO RST:
The low level alarm is automatically cleared as the
level rises above the LO ALARM set point.
MANUAL:
The alarm will remain on until the RESET button is
pressed by the operator.
MODE
In
PUMP
mode, as the level value rises above a set point,
the controller will switch
ON
the corresponding output relay and
it will remain
ON
until the level drops below the set point (the
PUMP
mode is used for pump down or emptying applica-
tions).
In
PUMP
mode, the relays turn
ON
as the level drops below
the set points and remains
ON
until the level rises above the
set point (the
PUMP
mode is used for pump up or filling
applications).
RUN SIG
USED/UNUSED
USED:
The pump run indication LEDs are dependent on input
signals 1, 2, 3, 4 from motor starter auxiliary contacts.
UNUSED:
The pump run indication LEDs are on when the output
relays for pump control are energized.
RES
CTRS
RESET ALL COUNTERS
Enter 12 in this field and all counters will be reset to
zero.
PRIMEX ™ 14 SP6R-LSC Level Controller User Manual