background image

 

HI ALARM

 

 

AUTO RST / MANUAL

 

 

AUTO RST:

  The high level alarm is automatically cleared as the    

 

 

 

 

level drops below the HI ALARM set point. 

 

 

MANUAL:

 

The alarm will remain on until the RESET button is    

 

 

 

 

pressed by the operator.

 LO 

ALARM 

 

AUTO RST / MANUAL

 

 

AUTO RST:

  The low level alarm is automatically cleared as the    

 

 

 

 

level rises above the LO ALARM set point. 

 

 

MANUAL:

 

The alarm will remain on until the RESET button is    

 

 

 

 

pressed by the operator.

 MODE 

In 

PUMP 

 

mode, as the level value rises above a set point,  

 

 

 

the controller will switch 

ON

 the corresponding output relay and  

 

 

 

it will remain 

ON

 until the level drops below the set point (the  

 

 

 

PUMP 

 mode is used for pump down or emptying applica-  

 

  

tions).

 

    

In 

PUMP 

 mode, the relays turn 

ON

 as the level drops below  

 

 

 

the set points and remains 

ON

 until the level rises above the  

 

 

 

set point (the 

PUMP 

 

mode is used for pump up or filling    

 

  

applications).

 

RUN SIG  

USED/UNUSED

 

 

USED:

 

The pump run indication LEDs are dependent on input  

 

 

 

 

signals 1, 2, 3, 4 from motor starter auxiliary contacts. 

 

 

UNUSED:

 

The pump run indication LEDs are on when the output  

 

 

 

 

relays for pump control are energized.

 RES 

CTRS 

 

RESET ALL COUNTERS

 

 

 

 

Enter 12 in this field and all counters will be reset to    

 

 

  zero.

PRIMEX ™                                                                                            14                                                               SP6R-LSC Level Controller User Manual

Summary of Contents for SP6R-LSC

Page 1: ...L BAR GRAPH 4 20 mA INPUT AUTOMATIC AL TERNATION MOTOR STATUS LEDs User Manual SP6R LSC CONTROLLER Ashland OH 800 363 5842 Clearwater FL 800 349 1905 Detroit Lakes MN 888 342 5753 Milford OH 513 831 9...

Page 2: ...ns Electrical Connections 8 10 8 10 Function Keys Displays Function Keys Displays 11 11 Setting Up Levels and Simulation Setting Up Levels and Simulation 11 12 11 12 Configuration Configuration 13 15...

Page 3: ...indication Form C SPDT contacts rated at 10A at 240 VAC LEVEL DISPLAY Eight character alpha numeric LED for process value and program parameters POWER 24 VDC 10 200 mA nominal 400 mA max OPERATING TE...

Page 4: ...figured for pump down or pump up applications SP6R LSC LEVEL CONTROLLER INTRODUCTION The standard SP6R LSC lift station controller kit contains see Figure 2 on page 5 of this manual one SP6R LSC lift...

Page 5: ...Disconnect power before installing or servicing this product A qualified service person must install and service this product according to applicable electrical codes EXPLOSION OR FIRE HAZARD Do not...

Page 6: ...emp High Level Lag Pump Lead Pump Low Level FIGURE 1 Dimensions and panel cut out Dimensions are indicative and may be subject to change without notification INSTALLATION DIMENSIONAL DATA PRIMEX 5 SP6...

Page 7: ...PRIMEX 6 SP6R LSC Level Controller User Manual PANEL CUT OUT TEMPLATE FOR SP6R LSC LIFT STATION CONTROLLER 8 6 218 mm 4 7 16 112 mm cut along dotted line...

Page 8: ...FIGURE 2 Standard SP6R LSC duplex lift station controller kit INSTALLATION DIMENSIONAL DATA PRIMEX 7 SP6R LSC Level Controller User Manual...

Page 9: ...is pro tected with an overall shield connect the shield to terminal 3 Terminal 4 and 5 must be connected if an output follower is not required If no valid input is present the controller will flash SE...

Page 10: ...FIGURE 6 Loop Powered Transducer Connection FIGURE 7 Self Powered Signal Connection PRIMEX 9 SP6R LSC Level Controller User Manual...

Page 11: ...240 VAC fuse protection is required indi vidually or as a group Motor starters auxiliary contacts Thermal switches in motor winding Normally closed open on over temperature Seal fail contact from seal...

Page 12: ...nger active NOTE The display automatically returns to level after 20 seconds of inactivity regardless of where it was left Pressing once will increment the current value by one unit Pressing and holdi...

Page 13: ...ETTING UP LEVELS FIGURE 8 Example of how to move from level display screen LO LEVEL Low level alarm set point STOP LD Stop lead pump level set point STOP LAG Stop lag pump level set point STAR LD Star...

Page 14: ...Percentage NONE Blank No Units Displayed When you are at the item you wish to edit press the ENTER key and the original value for the item selected will flash Use the UP and DOWN arrow keys to change...

Page 15: ...r before starting lag pump Set from one second to 600 seconds SEAL FLT LED ONLY LOCKOUT LAG ONLY LED ONLY In the event of a seal failure the pump will still be allowed to run and the seal fail light w...

Page 16: ...the corresponding output relay and it will remain ON until the level drops below the set point the PUMP mode is used for pump down or emptying applica tions In PUMP mode the relays turn ON as the leve...

Page 17: ...lo0alarm 0000mode 0run0sig res0ctrs FIGURE 9 Use the arrow keys to navigate through these menu items NOTE Eight 8 seconds of inactivity no keys pressed will terminate the con figuration menu and exit...

Page 18: ...OOFFSET 99 9 999 9 0 0 FT OLAGOTMR 1 0 600 3 0 SEC SEALOFLT OTHERMAL HIOALARM LOOALARM OOOOMODE PUMPXX PUMPXX PUMPXX ORUNOSIG USED UNUSED UNUSED RESOCTRS 0 0 0 CONFIGURATION MODE PARAMETERS FT IN CM M...

Page 19: ...5 0 FT STAROLAG 0 0 999 9 6 0 FT HIOLEVEL 0 0 999 9 7 0 FT ALTERNAT AUTO OETM1OHR READ ONLY OETM2OHR READ ONLY OOOOOEC1 READ ONLY OOOOOEC2 READ ONLY SIMULATE RUN MODE PARAMETERS LEVEL DISPLAY 4 mA va...

Page 20: ...controller can be configured for pump up or pump down applications Applications include level monitoring pressure temperature flow and analytical NEMA 4X The SP6R Set Point Controller is also availab...

Reviews: