FLOW MONITORING SETUP (PREMIUM)
Volumetric flow measurement is available when a level transducer is used in a cylindrical tank. The
Pump Watch
™
Express unit calculates the volume of liquid based on the level. The flow is calculated
by using the volume and the fill/discharge times. The in-flow and the discharge flow is measured. The
Flow Calc. Level set points are not used for controlling the pump. They are used for volumetric flow
calculation. The flow calculation is based on the diameter of the tank, the Start Flow Calc. and Stop
Flow Calc. level set points, and the fill and discharge times. Both In-Flow and Discharge flow are
calculated during every cycle.
Tank Diameter:
Enter the tank diameter in Ft.
Flow Calc. Start Level:
See below (in Ft.)
Flow Calc. Stop Level:
See below (in Ft.)
Important notes on flow setup:
Set Flow Calc. Start Level at least 4” below the pump start level.
Set Flow Calc. Stop Level at least 4” above the pump stop level.
The flow accuracy is better with longer cycle times (2 minutes or more).
PRIMEX
®
32 Pump Watch
™
Express User Manual
When using a rectangular tank,
the equivalent diameter would
be:
Example: A 10X10 tank would
equate to a diameter of 11.28.
Enter this value and get the
flow calculations as if it was a
cylindrical tank.
L= length, W= width.
LxW/
d=2
PUMP DATA
The Pump Data screen is for information only. It is a record on the pump HP, Volts, and FLA.
Pump HP:
Enter pump horsepower.
Pump Voltage:
Enter pump rated voltage.
Pump FLA:
Enter pump Full Load Amps (FLA) as shown on the nameplate.