46
Web Server - Manual
|
priceindustries.com
Web Server
PrTU-bAC-rTr (bACnet router Configuration)
If you want to log into the BAC Router to check any settings,
you need to set your machine to a Static IP; something close
to the IP address located on the front of the router, but not the
same.
Type the IP address (192.168.97.299 for example) on the
front of the router into a web browser, and a log in prompt will
appear.
Use: price and price1999 to get into the router
The IP address should match what is on the router itself, the MAC address should be set to 0 (zero) and the baud rate is defaulted
to 76800.
Device Instance is factory set. It is
recommended that you leave as is.
Each BAC-RTR comes with a factory
set IP Address and this should match
what is on the label of the BAC Router.
Price factory sets the MS/TP MAC
Address to 0, so that it won’t collide
with other devices on your network.
Zero is the recommended value.
Baud Rate is defaulted to 76800, and
the tolerance of the MS/TP should be
kept to Lenient.
3.0.6
BAcNet router coNFiGurAtioN