FAN FILTER UNIT - HIGH EFFICIENCY
INSTALLATION & SERVICE INSTRUCTIONS
Remove Diffuser Face with Quarter Turn Fasteners
STEP 3:
Make note of all wire locations for re-installation later. It is recommended to take a picture of all applicable wires.
STEP 4:
Open control box and disconnect wires at the terminal block, referencing applicable wiring diagram.
STEP 5:
Remove the 6 bolts to free the motor/blower assembly, using a 7/16” socket wrench (or equivalent).
STEP 6:
Remove motor/blower assembly.
STEP 7:
Inspect and/or replace parts.
STEP 8:
Replace with the new motor/blower assembly and reassemble by reversing the above steps.
NOTE:
For information on how to order replacement motor/blowers, contact your local Price Sales Representative. Visit Price’s
website (http://www.priceindustries.com/contact/reps-dealers) to locate your local Representative.
STEP 9:
Double check airflow to ensure that set point hasn’t changed. applicable speed controller found on pages X-X
36
priceindustries.com | FAN FILTER UNIT - HIGH EFFICIENCY - Manual
FAN FILTER UNIT - HIGH EFFICIENCY - Manual | priceindustries.com