SECTION 06B: ELECTRICAL
4
MID 188 PSID # 119 Brk Lts Sens (A36 JB:13)
Type of
fault:
FMI
Description:
Fault Condition:
Possible
Symptoms:
Possible Causes:
FMI 3
Shorted High Voltage above
normal on A36 JB:13
Stop lights
always ON
A36 module failure
A51 module failure
Connector C4 corroded
Connector C2 corroded
Connector C21 corroded
Circuit 78 shorted to battery
Circuit 79A shorted to battery
Circuit 953 shorted to battery
FMI 4
Shorted Low
Voltage below normal
on A36 JB:13
Stop lights not
working
A36 module failure
Se19 failure
Se19A failure
Connector C4 corroded
Connector C2 corroded
Connector C21 corroded
Circuit 78 shorted to ground
Circuit 79A shorted to ground
Circuit 953 shorted to ground
MID 188 PSID # 108 Ceiling Door Lt (A44 J1:5)
Type of
fault:
FMI
Description:
Fault Condition:
Possible
Symptoms:
Possible Causes:
FMI 3
Shorted High Voltage present on
output A44 J1:5 but
output not active
L17 always ON
A44 module failure
Connector C45 corroded
Circuit 35 shorted to battery
FMI 4
Shorted Low
Output A44 J1:5
shorted to ground
L17 not
working
A44 module failure
Connector C45 corroded
Circuit 35 shorted to ground
FMI 5
Open Circuit
A44 module does not
detect L17
L17 not
working
A44 module failure
L17 open circuit
Circuit 35 open
FMI 6
Current
above normal
Output A44 J1:5
internal software fuse
active for overcurrent
L17 not
working
A44 module failure
Connector C45 corroded
Circuit 35 shorted to ground
MID 188 PSID # 124 Center Flash LH (A50 J1:5)
Type of
fault:
FMI
Description:
Fault Condition:
Possible
Symptoms:
Possible Causes:
FMI 3
Shorted High Voltage present on
output A50 J1:5 but
output not active
L70 always ON
A50 module failure
Connector C15 corroded
Connector C21 corroded
Circuit 21A shorted to battery
FMI 4
Shorted Low
Output A50 J1:5
shorted to ground
L70 not
working
A50 module failure
Connector C15 corroded
Connector C21 corroded
Circuit 21A shorted to ground
FMI 6
Current
above normal
Output A50 J1:5
internal software fuse
active for overcurrent
L70 not
working
A50 module failure
Connector C15 corroded
Connector C21 corroded
Summary of Contents for X3-45 2016
Page 4: ......
Page 16: ...Section 00 GENERAL INFORMATION PA1593 12 FIGURE 12 METRIC US STANDARD CONVERSION TABLE 00005...
Page 17: ...Section 00 GENERAL INFORMATION 13 PA1593 FIGURE 13 CONVERSION CHART 00006...
Page 18: ......
Page 26: ......
Page 58: ......
Page 72: ...Section 04 EXHAUST AND AFTERTREATMENT SYSTEM PA1593 14 7 TORQUE SPECIFICATIONS...
Page 73: ...SECTION 04 EXHAUST AND AFTERTREATMENT SYSTEM PA1593 15...
Page 74: ...Section 04 EXHAUST AND AFTERTREATMENT SYSTEM PA1593 16...
Page 76: ......
Page 96: ......
Page 134: ......
Page 176: ...SECTION 06B ELECTRICAL 38 overcurrent working Circuit 306 shorted to ground...
Page 180: ......
Page 202: ......
Page 205: ...Section 09 PROPELLER SHAFT PA1593 3 FIGURE 1 PROPELLER SHAFT ASSEMBLY 09002...
Page 256: ......
Page 268: ......
Page 295: ...SECTION 16 SUSPENSION PA1593 9 2 5 TORQUE SPECIFICATIONS...
Page 296: ...Section 16 SUSPENSION PA1593 10...
Page 297: ...Section 16 SUSPENSION PA1593 11...
Page 314: ......
Page 380: ......
Page 388: ......
Page 413: ...Section 22 HEATING AND AIR CONDITIONING PA1593 15 FIGURE 18 REFRIGERANT CIRCUIT CENTRAL SYSTEM...
Page 433: ...Section 22 HEATING AND AIR CONDITIONING PA1593 35 FIGURE 36 CENTRAL HEATING SYSTEM COMPONENTS...