Section 06: ELECTRICAL
PA1593
25
Problem/Symptom
Probable Causes
Actions
Response ModA54, Active” indicates
a power problem on the module. (A
CAN network problem would show
the same message but doesn't
produce this symptom).
3. Check / reset circuit breaker CB5
4. Check / replace fuse F67 , F68
5. Probe gray connector on module to
see if it is powered.
HVAC condenser fans not
functioning in speed 1
Module A54 is not powered
or is faulty
1. Check the
Diagnostics
menu of
Driver Information Display (DID).
Select
Fault Diagnostics
and
Electrical System
. The message “No
Response ModA54, Active” indicates
a power problem on the module. (A
CAN network problem would show
the same message but doesn't
produce this symptom).
2. Check / reset circuit breaker CB5
3. Check / replace fuse F67 , F68
4. Probe gray connector on module to
see if it is powered.
Fire alarm telltale light
and audible alarm always
ON and there is no fire or
high temperature in the
engine compartment
Short-circuited fire sensor or
defective sensor
Prior to start the vehicle, cycle the ignition
key to the ON position, OFF position and
then ON position again and then start the
vehicle. This will deactivate the fire alarm
function. This has to be repeated each
time the vehicle is re-started
The vehicle is parked and
the electrical horn is acti-
vated to indicate a fire in
the engine compartment
but there is no fire
Short-circuited fire sensor or
defective sensor
Cycle the ignition switch between the ON
and OFF position twice within 3 seconds.
This will deactivate the fire alarm function.
This has to be repeated each time the
vehicle is parked
A single light, a group of
LED lights or another
function of the vehicle is
not functioning
The multiplex outputs are
protected in current by an
internal “soft-fuse”. When an
output is shorted, it turns
OFF and stays OFF until the
"soft-fuse" is reset
Turn the ignition switch to the OFF
position and turn to the ON position again.
This resets all "soft –fuses"
No backlighting in the
instrument cluster
Circuit breaker CB10 is
tripped or fuse F20 blown
Check / reset circuit breaker CB10
Check / replace fuse F20
Summary of Contents for X3-45 2016
Page 4: ......
Page 16: ...Section 00 GENERAL INFORMATION PA1593 12 FIGURE 12 METRIC US STANDARD CONVERSION TABLE 00005...
Page 17: ...Section 00 GENERAL INFORMATION 13 PA1593 FIGURE 13 CONVERSION CHART 00006...
Page 18: ......
Page 26: ......
Page 58: ......
Page 72: ...Section 04 EXHAUST AND AFTERTREATMENT SYSTEM PA1593 14 7 TORQUE SPECIFICATIONS...
Page 73: ...SECTION 04 EXHAUST AND AFTERTREATMENT SYSTEM PA1593 15...
Page 74: ...Section 04 EXHAUST AND AFTERTREATMENT SYSTEM PA1593 16...
Page 76: ......
Page 96: ......
Page 134: ......
Page 176: ...SECTION 06B ELECTRICAL 38 overcurrent working Circuit 306 shorted to ground...
Page 180: ......
Page 202: ......
Page 205: ...Section 09 PROPELLER SHAFT PA1593 3 FIGURE 1 PROPELLER SHAFT ASSEMBLY 09002...
Page 256: ......
Page 268: ......
Page 295: ...SECTION 16 SUSPENSION PA1593 9 2 5 TORQUE SPECIFICATIONS...
Page 296: ...Section 16 SUSPENSION PA1593 10...
Page 297: ...Section 16 SUSPENSION PA1593 11...
Page 314: ......
Page 380: ......
Page 388: ......
Page 413: ...Section 22 HEATING AND AIR CONDITIONING PA1593 15 FIGURE 18 REFRIGERANT CIRCUIT CENTRAL SYSTEM...
Page 433: ...Section 22 HEATING AND AIR CONDITIONING PA1593 35 FIGURE 36 CENTRAL HEATING SYSTEM COMPONENTS...