Page 30
2.1.10. Calibration Examples
a) Pressure Transmitter Calibration
Use the PCON-Y18-LP
TPS
source (24 Vdc) to power up a two-wire transmitter
and connect the current as illustrated below.
Select
mA
(current) in the
Input
(Auxiliary)
menu and configure the Pressure Control parameters.
Fig. 43
- Pressure Transmitter Calibration
Readings of the mA input can be scaled to pressure through the
SCALE
option
(see section
2.1.9.
). Thus, the error between the input and the output of the pressure
transmitter is easily calculated.