PRESYS
Instruments
DMY-2030-TOT
Light
Operation
Page 23
The table below refers to the ranges of the parameters shown in figure 15.
Mnemonic
Parameter
Range
Factory Value
Units
SP
alarm setpoint
-1009 to 20019
25.0 - low alarm
75.0 - high alarm
EU
HYST
alarm hysteresis
0 to 250
1.0
EU
DELAY
delay for activating
the relay
0.0 to 3000.0
0.0
seconds
Level 4 - Output
Level 4 allows the configuration of
one analog output (Refer to figure 16).
Fig.16 - OUTPUT level options
The table below refers to the ranges of the parameters shown in figure 16.
Mnemonic
Parameters
Range
Factory
Value
Unit
LIM LOW
output signal associated
to Eng Low
0.0 to 100.0
0.0
%
LIM HIGH
output signal associated
to Eng High
0.0 to 100.0
100.0
%
ENG LOW
display indication
associated to Lim Low
-1009 to 20019
0.0
EU
ENG HIGH
display indication
associated to Lim High
-1009 to 20019
100.0
EU
presys