INSTALLING OXIDIZING UNIT UPGRADE 

(return side plenum only)

1. Cut a 1.75” - 2” hole for the unit.
2. Attach the unit to the air duct using the four self-tapping sheet metal screws provided.

    (Airflow direction is marked on the unit.)
3. Route oxidizing unit’s cord to the power supply.
4. Disconnect blue wires from terminal 1 and 2 and reconnect blue wires to terminal 5 and 6. See illustration #1
5. Remove hole plug from bottom of germicidal unit by pinching plug from inside of unit and pushing from the back.
6. Route the oxidizing unit’s cord into the power supply and connect blue wires to terminal 1 and 2  and red wires   

    to terminal 3 and 4.
7. Wrap strain relief around base of cord, pinch with a pliers and snap into position.

INSTALLING GERMICIDAL UNIT UPGRADE 

(return or supply side plenum)

1. Remove two thumb nuts holding moisture resistant lamp socket to mounting plate and remove from the plate.
2. Using the lamp mounting plate as a template, draw the hole pattern on the air duct in a suitable location.
3. Using a 1 1/4 inch Vari Bit, make two holes side by side. Clean off excess metal between the two 

    holes with tin snips.  Alternately cut a 2” hole.
4. Peel off the gasket backing from lamp mounting plate and center over hole. Secure using four self-tapping sheet 

    metal screws provided.

5. Route the germicidal lamp connector’s cord to the power supply.
6. Disconnect blue wires from terminal 1 and 2 and reconnect blue wires to terminals 5 and 6. See illustration #1.
7. Remove hole plug from bottom of germicidal unit by pinching plug from inside of unit and pushing from the back.
8. Route the germicidal lamp connector’s cord into the power supply and connect blue wires to terminal 1 and 2  

    and red wires to terminal 3 and 4.
9. Wrap strain relief around base of cord, pinch with a pliers and snap into position.

10. Taking care not to touch the glass, hold the lamp by the end cap and insert fully into the base plate.
11. Insert the moisture resistant lamp socket over the plastic lamp end fitting over the mounting studs.

    Secure using the two thumb nut. (Photo A)

UPGRADING SINGLE LAMP TO DUAL LAMP OPERATION

This unit can be upgraded to include one germicidal lamp and one oxidation unit. 

For dual germicidal lamp operation please use our model MUV7-100DR.

INSTALLING THE OXIDIZING UNIT

 

(return side plenum only)

1. Cut a 1.75” - 2” hole for the unit.
2. Attach the unit to the air duct using the four self-tapping sheet metal screws provided. 

   (Airflow direction is marked on the unit.)
3. Route oxidizing unit’s cord from the power supply, to the oxidizing unit and connect mid-cord connector.  

    Be sure to line up arrows on the connector. (see photo B)

Summary of Contents for MUV7-50DR

Page 1: ...1 200 pi carr s 3 Assurez vous de toujours d brancher avant l installation ou le service 4 Ne pas regarder la lampe directement avec les yeux Si n cessaire de le faire veuillez porter les lunettes de...

Page 2: ...de plenum 1 Unplug mid cord connector s by pressing the lock release marked PRESS on the connector see photo B Remove two thumb nuts holding moisture resistant lamp socket to mounting plate and remove...

Page 3: ...ver hole Secure using four self tapping sheet metal screws provided 5 Route the germicidal lamp connector s cord to the power supply 6 Disconnect blue wires from terminal 1 and 2 and reconnect blue wi...

Page 4: ...idizing unit is not installed you may allow unit to run continuously The multi voltage ballast is self adjusting and operates with voltages from 120 240 VAC For 120V wiring connect the black wire to L...

Page 5: ...e by side Clean off excess metal between the two holes with tin snips 3 Peel off the adhesive backing of the gasket on backside of mounting plate 4 Center mounting plate on hole 5 Use four self tappin...

Page 6: ...ss portion of the lamp with bare hands 4 Carefully slide the moisture lamp socket with lamp through the mounting plate into duct fitting over the mounting studs and secure using the two thumb nuts and...

Page 7: ...of two years This warranty does not cover lamps broken during shipping installation or as a result of improper handling All returns are routed through your contractor wholesaler and must be approved a...