PD6830 Pulse Input Rate/Totalizer Instruction
Manual
33
Error Message (
Error
)
An error message indicates that the calibration or scaling process was not successful.
After the error message is displayed, the meter reverts to input 2 during calibration or
scaling, allowing the appropriate input signal to be applied or programmed.
The error message might be caused by any of the following conditions:
1.
Input signal is not connected to the proper terminals or it is connected backwards.
2.
Minimum input span requirements not maintained.
3.
Input 1 signal inadvertently applied to calibrate input 2.
Minimum Input Span
The minimum allowed input span is 1 Hz, which is the minimum difference between input
1 and input 2 signals required to complete the calibration or scaling of the meter.
Summary of Contents for ProtEX-RTP PD6830
Page 55: ...PD6830 Pulse Input Rate Totalizer Instruction Manual 55...
Page 57: ...PD6830 Pulse Input Rate Totalizer Instruction Manual 57 NOTES...
Page 58: ...PD6830 Pulse Input Rate Totalizer Instruction Manual 58 NOTES...
Page 59: ...PD6830 Pulse Input Rate Totalizer Instruction Manual 59 NOTES...