background image

PD6720 Field-Mount Loop-Powered Rate/Totalizer 

Instruction Manual 

 

21

 

Programmable Exponent  
Linearization (

Prog.E

The programmable exponent can be used to linearize 
the signal from level transmitters in open-channel flow 
applications using weirs and flumes. 

 

The PD6720, in combination with an ultrasonic level 
transmitter, makes for an economical way to measure 
and display open channel flow rate and total in most 
weirs and flumes. A guide such as the ISCO Open 
Channel Flow Measurement Handbook can provide 
the user with all the information needed: the exponent 
used in the flow equation for the desired flow units 
and the flow rate for any given head height. 

For example, to display the open channel flow rate 
from a 3" Parshall flume, the ISCO handbook advises 
the exponent is 1.547 and at the maximum head 
height of 3.0 feet, the flow rate is 3.508 MGD. 

3" Parshall Flume Discharge Table 

Formula:   

CFS 

= 0.9920 

H

1.547

 

 

 

GPM 

= 445.2 

H

1.547

 

 

 

MGD 

= 0.6411 

H

1.547

 

Where:    

H  

= Head in feet 

Table 12-3 

Head (Feet) 

CFS 

GPM 

MGD 

3.00 

5.428 

2436 

3.508 

ISCO Open Channel Flow Measurement Handbook, 3

rd

 edition 

With this information the PD6720 should be 
programmed in the following fashion. This setup 
assumes the level transmitter is programmed to 
output 20 mA at the maximum head height of 1.10 
feet; but any mA value at a head height with a known 
flow rate may be used. 

Function 

Desired 

Programming 

Open 
Channel 
Flow 

3" Parshall flume 

Set Programmable Exponent to 
1.547 

Flow Rate 

Millions of Gallons 
per Day (MGD) 

Set 4 mA = 0 
20 mA = 3.508 
Time base = Day 

Total 

Millions of Gallons 

Set Totalizer Conversion Factor = 1 

(password protect 

“total” to 

avoid accidental reset) 

Non-
Resettable 
Grand Total 

Program meter so 
grand total can 
never be reset 

Set non-resettable grand total 
password 

Display 

Display Flow Rate, 
Total, and Grand 
Total 

Set upper display for Grand 
Total and lower display to 
toggle between rate and total. 

 

Input Signal Filter (

FILTER

 

The noise filter is available for unusually noisy signals 
that cause an unstable process variable display. The 
noise filter averages the input signal over a certain 
period. The filter level can be set to low (

LO

), medium 

(

med

), high (

HI

), or off (

OFF

). The higher the filter 

setting, the longer the averaging time and so the 
longer the display may take to find its final value.  
The filter contains a noise filter bypass feature so that 
while small variations in the signal will be filtered out, 
large, abrupt changes to the input signal are 
displayed immediately. 

Internal Calibration (

ICAL

There is 

no need to recalibrate

 the meter for 

milliamps when first received from the factory. 
The meter is 

factory calibrated

 for milliamps prior 

to shipment. The calibration equipment is traceable 
to NIST standards. 

The internal calibration allows the user to scale the 
meter without applying a signal. The use of a 
calibrated signal source is necessary to perform the  
internal calibration of the meter. Check calibration  
of the meter at least every 12 months. 

Notes:

 The signal source must have a full-scale accuracy 

of 0.002% or better between 4 and 20 mA in order to 
maintain the specified accuracy of the meter. 
Allow the meter to warm up for at least 15 minutes before 
performing the internal calibration procedure. 

The 

Internal

 

calibration

 menu is part of the 

Advanced

 

features menu.  
Press and hold the 

MENU

 button for 5 seconds to  

enter the 

Advanced

 features menu. Press the 

Up  

arrow button to scroll to the 

Internal Calibration

 menu 

(

ICAL

) and press 

Enter

The meter displays 

4.000

 mA. Apply a 4.000 mA  

signal and press 

Enter

. The display flashes for a  

moment while the meter is accepting the signal. 
After the signal is accepted, the meter displays 

20.000

 

mA. Apply a 20.000 mA signal and press 

Enter

. The 

display flashes for a moment while the meter is  
accepting the signal. 

Error Message (

SPAN

 

ERROR

An error message indicates that the calibration process 
was not successful. After the error message is 
displayed, the meter will revert to input 2 calibration 
settings. The error message might be caused by 
inadvertently leaving the signal at the previous level or 
not maintaining the minimum span. Press the Menu 
button to cancel the current calibration process if 
necessary. 

Information

 

(

INFO

)

 

The 

Internal

 

calibration

 menu is part of the 

Advanced

 

features menu. It shows software identification 
number and version number. To determine the 
software version of a meter: 
Go to the 

Information

 menu (

INFO

) and press 

Enter

 

button. 
Continue pressing 

Enter

 to scroll through the 

software release number and software version. 
Following the information display, the meter will exit 
the 

Advanced

 features menu and return to run mode. 

 

 

Summary of Contents for PD6720 Series

Page 1: ...Display Rate in Units per Second Minute Hour or Day Display Open Channel Flow with Programmable Exponent Feature Open Collector Pulse or Alarm Output Display Mountable at 0 90 180 270 SafeTouchTM Thro...

Page 2: ...Terms Conditions on www predig com for complete details 2020 Precision Digital Corporation All rights reserved Introduction The PD6720 is a rugged field mount loop powered rate totalizer fully featur...

Page 3: ...ime Base t base 15 Setting the Total Conversion Factor totCF 15 Manual or Automatic Total Reset Function t rST 16 Setting the Tag Display tag 16 Setting Up the Password PASSWRD 17 Locking the Meter 17...

Page 4: ...Enclosure Dimensions Side Cross Section View 7 Figure 3 Connector Board 8 Figure 4 Connections without Backlight 9 Figure 5 Connections with Loop Powered Backlight 9 Figure 6 Connections with Externa...

Page 5: ...Environmental Operating temperature range 40 to 75 C Storage temperature range 40 to 75 C Relative humidity 0 to 90 non condensing Connections Screw terminals accept 12 to 22 AWG wire Enclosure NEMA...

Page 6: ...able from 0 to 99 999 seconds Open Collector Output Rating Isolated open collector sinking NPN 30 VDC 150 mA max Alarm Output Assign to rate for high or low alarm trip point Assign to total for total...

Page 7: ...and set the display module aside Unpacking Remove the meter from box Inspect the packaging and contents for damage Report damages if any to the carrier If any part is missing or the meter malfunction...

Page 8: ...t from external supply OUTPUT NPN open collector output positive OUTPUT NPN open collector output negative RESET Contact closure alarm acknowledge pull up to 3 VDC RESET Contact closure alarm acknowle...

Page 9: ...ions are made to two terminals labeled RESET Connect to a contact closure source such as a relay or a pushbutton as shown in Figure 7 Figure 7 Reset Connections Open Collector Output Connections Outpu...

Page 10: ...sors are disabled when a mechanical button is pressed and will automatically be re enabled after 60 seconds of inactivity The SafeTouch buttons are designed to filter normal levels of ambient interfer...

Page 11: ...nds to access the Advanced features of the meter Right Reset Button Press the Right arrow button to move to the next digit or decimal position during programming Up Display Button Press the Up arrow b...

Page 12: ...ogram menu sCalE Scale Enter the Scale menu Cal Calibrate Enter the Calibrate menu Inpt1 Input 1 Calibrate input 1 signal or program input 1 value DspL1 Display 1 Program display 1 value Inpt2 Input 2...

Page 13: ...w to select next digit and Up arrow to increment digit The digit being changed blinks Press the Enter button at any time to accept a setting or MENU button to exit without saving changes The decimal p...

Page 14: ...functions are exclusive of each other The meter uses the last function programmed Only one of these methods can be employed at a time The Scale and Calibrate functions can use up to 32 points default...

Page 15: ...complete the calibration or scaling of the meter The minimum span is 0 10 mA If the minimum span is not maintained the meter reverts to input 2 allowing the appropriate input signals to be applied Re...

Page 16: ...on choose man dsabl To reset total upon total alarm set point choose auto enter a time delay t dly and proceed to programming the set point see Alarm Output alrm on page 19 Press the Enter button at a...

Page 17: ...returns to its password protected condition Disabling Password Protection To disable the password protection access the Password menu and enter the correct password twice as shown below The meter is n...

Page 18: ...total Set Set Point Program set point Reset Reset Point Program reset point Pulse Pulse Output Program pulse output Scaler Count MAX HZ Frequency Program pulse output maximum frequency Funct Function...

Page 19: ...deadband is one display count If set and reset points are programmed the same output will reset one count below set point Total alarm trip point program total set point Alarm reset is triggered by tot...

Page 20: ...rent source instead of using input scaling This process will override previously programmed scaling points Apply a live signal using a known accurate signal source InP 1 32 and then enter the correspo...

Page 21: ...ging time and so the longer the display may take to find its final value The filter contains a noise filter bypass feature so that while small variations in the signal will be filtered out large abrup...

Page 22: ...he factory defaults Instructions to load factory defaults Enter the Advanced features menu Press and hold Reset button when INFO is shown Press Enter when RESET DFALTS prompt is shown Note If Enter is...

Page 23: ...exit Max Min display readings Display response is too slow Check filter setting to see if it can be lowered to LO or OFF If the display locks up or the meter does not respond at all Perform hard rese...

Page 24: ...on or increment digit Cycle through maximum minimum and mA display mode ENTER Accept selection value and move to next selection Acknowledge alarms Max Min Mode While in Run Mode pressing Up Arrow will...

Page 25: ...990 www predig com LIM6720_C SFT049 Ver 1 200 up 07 20 Contact Precision Digital Technical Support Call 800 610 5239 or 508 655 7300 Fax 508 655 8990 Email support predig com Sales Support Call 800 34...

Reviews: