PD6720 Field-Mount Loop-Powered Rate/Totalizer 

Instruction Manual 

 

20

 

Advanced Function Selection 
(

FUNCTN

The 

Advanced Function

 menu is used to select the 

advanced function to be applied to the input: linear, 
square root, programmable exponent, or round 
horizontal tank volume calculation. The multi-point 
linearization is part of the linear function selection. 

Meters are set up at the factory for linear function with 
2-point linearization. The linear function provides a 
display that is linear with respect to the input signal. 

Multi-Point Linearization (

lnear

Up to 32 linearization points can be selected under 
the 

Linear

 function. The multi-point linearization can 

be used to linearize the display for non-linear signals 
such as those from level transmitters used to 
measure volume in odd-shaped tanks or to convert 
level to flow using weirs and flumes that require a 
complex exponent. These points are established via 
direct entry (

SCALE

) or with a live calibration signal 

source (

CAL

). 

 

 

Multi-Point Scaling (

SCALE

The multi-point scaling is entered after selecting the 
number of points (

noPtS

). The input signal levels  

(

InP 1-32

) for up to 32 points, along with the 

corresponding meter reading (

dSP 1-32

) should be 

entered for each linearization point. 

Multi-Point Calibration (

CAL

The meter can be calibrated using a current source 
instead of using input scaling. This process will 
override previously programmed scaling points.  
Apply a live signal using a known accurate signal 
source (

InP

 

1-32

) and then enter the corresponding 

meter reading (

disp 1-32

) for that input signal level. 

The use of a calibrated signal source is strongly 
recommended. 

Important Navigation Note 

After entering the last display value, the linearization 
entries must be saved (

SAUE?

) before they are put into 

effect. However, you may move past this selection 
using the Up arrow key if you need to go back and 
correct and earlier entry. Once confident in the entries, 
you must navigate back to the Save menu screen 
(

SAUE?

) and press the Enter key to save the changes. 

 

Square Root Linearization (

Squar

The square root function can be used to linearize  
the signal from a differential pressure transmitter  
and display flow rate in engineering units. 

 

PD6720 Displaying Flow Rate by Extracting Square Root 

from DP Transmitter Signal. 

 

Low-Flow Cutoff (

CUTOFF

The low-flow cutoff feature allows the meter to be 
programmed so that the often-unsteady output from a 
differential pressure transmitter, at low flow rates, 
always displays zero on the meter. The default cutoff 
is zero to prevent negative readings, but this may be 
overridden to allow them. 
The cutoff value may be programmed from -0 to 
99999. Below the cutoff value, the meter will display 
zero. Selecting either square root or programmable 
exponent will set the cutoff value to 0. Program the 
cutoff value to 0 to disable. 

 

Summary of Contents for PD6720 Series

Page 1: ...Display Rate in Units per Second Minute Hour or Day Display Open Channel Flow with Programmable Exponent Feature Open Collector Pulse or Alarm Output Display Mountable at 0 90 180 270 SafeTouchTM Thro...

Page 2: ...Terms Conditions on www predig com for complete details 2020 Precision Digital Corporation All rights reserved Introduction The PD6720 is a rugged field mount loop powered rate totalizer fully featur...

Page 3: ...ime Base t base 15 Setting the Total Conversion Factor totCF 15 Manual or Automatic Total Reset Function t rST 16 Setting the Tag Display tag 16 Setting Up the Password PASSWRD 17 Locking the Meter 17...

Page 4: ...Enclosure Dimensions Side Cross Section View 7 Figure 3 Connector Board 8 Figure 4 Connections without Backlight 9 Figure 5 Connections with Loop Powered Backlight 9 Figure 6 Connections with Externa...

Page 5: ...Environmental Operating temperature range 40 to 75 C Storage temperature range 40 to 75 C Relative humidity 0 to 90 non condensing Connections Screw terminals accept 12 to 22 AWG wire Enclosure NEMA...

Page 6: ...able from 0 to 99 999 seconds Open Collector Output Rating Isolated open collector sinking NPN 30 VDC 150 mA max Alarm Output Assign to rate for high or low alarm trip point Assign to total for total...

Page 7: ...and set the display module aside Unpacking Remove the meter from box Inspect the packaging and contents for damage Report damages if any to the carrier If any part is missing or the meter malfunction...

Page 8: ...t from external supply OUTPUT NPN open collector output positive OUTPUT NPN open collector output negative RESET Contact closure alarm acknowledge pull up to 3 VDC RESET Contact closure alarm acknowle...

Page 9: ...ions are made to two terminals labeled RESET Connect to a contact closure source such as a relay or a pushbutton as shown in Figure 7 Figure 7 Reset Connections Open Collector Output Connections Outpu...

Page 10: ...sors are disabled when a mechanical button is pressed and will automatically be re enabled after 60 seconds of inactivity The SafeTouch buttons are designed to filter normal levels of ambient interfer...

Page 11: ...nds to access the Advanced features of the meter Right Reset Button Press the Right arrow button to move to the next digit or decimal position during programming Up Display Button Press the Up arrow b...

Page 12: ...ogram menu sCalE Scale Enter the Scale menu Cal Calibrate Enter the Calibrate menu Inpt1 Input 1 Calibrate input 1 signal or program input 1 value DspL1 Display 1 Program display 1 value Inpt2 Input 2...

Page 13: ...w to select next digit and Up arrow to increment digit The digit being changed blinks Press the Enter button at any time to accept a setting or MENU button to exit without saving changes The decimal p...

Page 14: ...functions are exclusive of each other The meter uses the last function programmed Only one of these methods can be employed at a time The Scale and Calibrate functions can use up to 32 points default...

Page 15: ...complete the calibration or scaling of the meter The minimum span is 0 10 mA If the minimum span is not maintained the meter reverts to input 2 allowing the appropriate input signals to be applied Re...

Page 16: ...on choose man dsabl To reset total upon total alarm set point choose auto enter a time delay t dly and proceed to programming the set point see Alarm Output alrm on page 19 Press the Enter button at a...

Page 17: ...returns to its password protected condition Disabling Password Protection To disable the password protection access the Password menu and enter the correct password twice as shown below The meter is n...

Page 18: ...total Set Set Point Program set point Reset Reset Point Program reset point Pulse Pulse Output Program pulse output Scaler Count MAX HZ Frequency Program pulse output maximum frequency Funct Function...

Page 19: ...deadband is one display count If set and reset points are programmed the same output will reset one count below set point Total alarm trip point program total set point Alarm reset is triggered by tot...

Page 20: ...rent source instead of using input scaling This process will override previously programmed scaling points Apply a live signal using a known accurate signal source InP 1 32 and then enter the correspo...

Page 21: ...ging time and so the longer the display may take to find its final value The filter contains a noise filter bypass feature so that while small variations in the signal will be filtered out large abrup...

Page 22: ...he factory defaults Instructions to load factory defaults Enter the Advanced features menu Press and hold Reset button when INFO is shown Press Enter when RESET DFALTS prompt is shown Note If Enter is...

Page 23: ...exit Max Min display readings Display response is too slow Check filter setting to see if it can be lowered to LO or OFF If the display locks up or the meter does not respond at all Perform hard rese...

Page 24: ...on or increment digit Cycle through maximum minimum and mA display mode ENTER Accept selection value and move to next selection Acknowledge alarms Max Min Mode While in Run Mode pressing Up Arrow will...

Page 25: ...990 www predig com LIM6720_C SFT049 Ver 1 200 up 07 20 Contact Precision Digital Technical Support Call 800 610 5239 or 508 655 7300 Fax 508 655 8990 Email support predig com Sales Support Call 800 34...

Reviews: