PD6701 Field-Mount Loop-Powered Feet & Inches Level Meter 

Instruction Manual 

 

5

 

Specifications 

Except where noted all specifications apply to operation at +25°C. 

General 

Display 

Feet &  
Inches 

0.60" (15.2 mm) high  
0 to 699

FT

 11

15

/

16

 

IN 

7-segment, programmable  
1/16 or 1/8 fraction display 

Seven 
characters 
(Tag &/or 
Volume) 

0.4" (10.2 mm) high 
14-segment, 7-digits 

Tank Level 
Indicator 

20-segments 

Display 
Orientation 

Display may be mounted at 90° increments  
up to 270° from default orientation. 

Display 
Assignment 

Upper display: Feet & inches 
Lower display may be assigned to custom unit 
or tag, volume, volume and tag, percent 
height, percent height and tag, or off. 

Display 
Update Rate 

Ambient > -25°C: 2 Updates/Second  
Ambient < -25°C: 1 Update/5 Seconds 

Backlight 

White; Loop-powered or externally powered. 
Backlight can be enabled or disabled via 
alternative wiring of terminal block. Loop-
powered backlight brightness will increase as 
the input signal current increases. Externally 
powered backlight has consistent brightness. 

Externally 
Powered 
Backlight 

Voltage 
Range: 

Maximum Power 

9-36  
VDC 

9  
VDC 

12  
VDC 

24  
VDC 

36 
VDC 

 

0.2 W

 

0.25 W

 

0.5 W

 

0.75 W

 

 

Overrange 
And 
Underrange  

Level display flashes to 

699

FT

 

11

15

/

16

 

IN 

Volume display flashes 

9999999

 if overrange,  

-999999

 if underrange. 

Programming 
Method 

Four SafeTouch through-window buttons 
when cover is installed. Four internal 
pushbuttons when cover is removed. 

Noise Filter 

Programmable low (

LO

), medium (

MED

), high 

(

HI

), or off (

OFF

Recalibration 

Recalibration is recommended at least every 
12 months. 

Max/Min 
Display 

Max/Min readings reached by the process are 
stored until reset by the user or until power to 
the meter is turned off.  

Password 

Programmable password restricts modification 
of programmed settings. 

Non-Volatile 
Memory 

All programmed settings are stored in non-
volatile memory for a minimum of ten years if 
power is lost. 

Normal Mode 
Rejection 

64 dB at 50/60 Hz 

Environmental 

Operating temperature range: -40 to 75°C 
Storage temperature range: -40 to 75°C 
Relative humidity: 0 to 90% non-condensing 

Connections 

Screw terminals accept 12 to 22 AWG wire 

Enclosure 
 

NEMA 4X, IP65 plastic field enclosure  
Color: grey 
Three ¾" NPT threaded conduit openings.  
Two ¾" NPT plastic conduit/stopping plug with  
1.29" wrenching flats and screwdriver slot. 

Mounting 

May be mounted directly to conduit. Two 
slotted flanges for wall mounting or NPS 
1½" to 2½" or DN 40 to 65 mm pipe 
mounting. Se

Dimensions

 on pag

6

 

Overall 
Dimensions 

5.67" x 5.25" x 4.18" (W x H x D) 
(144 mm x 133 mm x 106 mm) 

Weight 

1.65 lbs (26.4 oz, 0.75 kg) 

Warranty 

3 years parts and labor. See Warranty 
Information and Terms & Conditions on 

www.predig.com

 for complete details. 

Input 

Input   

4-20 mA 

Accuracy  

±0.03% of calibrated span ±1 count 

Maximum  
Voltage Drop & 
Equivalent 
Resistance 

Without Backlight 
or with Externally 
Powered Backlight 

With Loop-Powered 
Backlight 

3.0 VDC @ 20 mA 

6.0 VDC @ 20 mA 

 

150 

Ω @ 20 mA 

300 

Ω @ 20 mA 

Temperature 
Drift 

50 PPM/

C from -40 to 75

C ambient 

Multi-Point  
Linearization 

2 to 32 points, level and volume  
independently programmed. 

Minimum Span 

Input 1 & Input 2: 0.10 mA 

Calibration 
Range 

An 

Error

 message will appear if input 1 

and input 2 signals are too close  
together. 

Input 
Range 

Minimum Span 
Input 1 & Input 2 

4-20 mA  

0.10 mA 

Input 
Overload 

Over current protection to 2 A max. 

HART  
Transparency 

The meter does not interfere with existing 
HART communications; it displays the 
4-20 mA primary variable and it allows the 
HART communications to pass through 
without interruption. 
The meter is not affected if a HART 
communicator is connected to the loop. 
The meter does not display secondary 
HART variables. 

 

Open Collector Output 

Rating 

Isolated open collector, sinking NPN 
30 VDC @ 150 mA max. 

Alarm Output 

Assign to level or volume for high or low 
alarm trip point. 

Deadband 

0-100% FS, user selectable 

Acknowledge 

Front panel ENTER button and external  
RESET terminals resets output and screen  
indication. 

 

 

 

Summary of Contents for PD6701

Page 1: ...Tag Volume or Percent Display Level in Feet Inches and Volume Percent or Decimal Height Simultaneously Display Mountable at 0 90 180 270 SafeTouchTM Through Window Button Programming 20 Segment Tank...

Page 2: ...1 is a rugged field mount loop powered indicator specifically designed for level applications in harsh environmental conditions The meter displays level in easy to read and understand feet inches and...

Page 3: ...es 12 Scaling the Meter SCaLe 13 Selecting Inch Fraction Display Mode FRACTN 13 Scaling the Tank Level Indicator PERCENT 13 Configuring the Lower Display DISPLAY 14 Setting the Tag TAG 14 Advanced Fea...

Page 4: ...e Dimensions Side Cross Section View 6 Figure 3 Connector Board 7 Figure 4 Connections without Backlight 8 Figure 5 Connections with Loop Powered Backlight 8 Figure 6 Connections with Externally Power...

Page 5: ...ower is lost Normal Mode Rejection 64 dB at 50 60 Hz Environmental Operating temperature range 40 to 75 C Storage temperature range 40 to 75 C Relative humidity 0 to 90 non condensing Connections Scre...

Page 6: ...rt damages if any to the carrier If any part is missing or the meter malfunctions please contact your supplier or the factory for assistance Pre Installed Conduit Plug The PD6701 is supplied with two...

Page 7: ...klight from external supply OUTPUT NPN open collector output positive OUTPUT NPN open collector output negative RESET Contact closure alarm acknowledge pull up to 3 VDC RESET Contact closure alarm ack...

Page 8: ...nnections are made to two terminals labeled RESET Connect to a contact closure source such as a relay or a pushbutton as shown in Figure 7 Figure 7 External Alarm Reset Acknowledge Connections Open Co...

Page 9: ...n Operation To actuate a button press and remove one finger to the window directly over the marked button area Remove finger to at least 4 inches away from the window in between button activations Saf...

Page 10: ...meter Right Reset Button Press the Right arrow button to reset the maximum or minimum value while it is being displayed see Up Display Button below Press the Right arrow button to move to the next di...

Page 11: ...1 8th Set display for 1 8th inch fractions PERCENT Percent Scale the tank indicator full and empty values 0 PCT 0 Percent Set the tank empty value 100 PCT 100 Percent Set the tank full value DISPLAY D...

Page 12: ...es made to settings prior to pressing ENTER are not saved Press the MENU button during Programming Mode to return to the previous menu selections Setting Numeric Values The numeric values are set usin...

Page 13: ...ng of the meter The minimum span is 0 10 mA Scale Error Message SPN ERR If the minimum span is not maintained the meter will show a span error SPN ERR and revert to input 2 allowing the appropriate in...

Page 14: ...ate second scale of the input process variable This is configured in Volume Display Scaling VOLSCAL on page 17 Percent full height shows the percent full of the tank height level indicator programmed...

Page 15: ...e Advanced features menu functions and messages in the order they appear in the menu Display Parameter Action Setting OUTPUT Output Enter output menu OFF Off Disable output ALARM Alarm Output Enter al...

Page 16: ...ibration parameters ICAL Internal Calibration Enter internal reference calibration 4mA 4 mA Calibrate input at 4 mA 20mA 20 mA Calibrate input at 20 mA ERRSPAN Error Span Error with calibration point...

Page 17: ...y and ALARM until the alarm condition is cleared The alarm status will show on the display even if the output is not wired Input Signal Filter FILTER The noise filter is available for unusually noisy...

Page 18: ...ment while the meter is accepting the signal After the signal is accepted the meter displays 20 mA Apply a 20 000 mA signal and press ENTER The display flashes for a moment while the meter is acceptin...

Page 19: ...meter will display the message LOCKED when the Menu button is pressed Press the Enter button while the message is being displayed and enter the correct password to gain access to the menu After exiti...

Page 20: ...ayed will reset that value to the current display value Press the DISPLAY button a third time and the meter will display LOOP MA on the lower display followed by the measured input current in milliamp...

Page 21: ...ostics menu and consult the recommendations described below Troubleshooting Tips Symptom Check Action No display or faint display Check input signal connections Perform hard reset by shorting S and S...

Page 22: ...lection or increment digit Cycle through maximum minimum and mA display mode ENTER Accept selection value and move to next selection Acknowledge alarms To enter the Advanced Features Menu hold the Men...

Page 23: ...655 8990 www predig com LIM6701_E SFT087 Ver 1 300 up 07 20 Contact Precision Digital Technical Support Call 800 610 5239 or 508 655 7300 Fax 508 655 8990 Email support predig com Sales Support Call 8...

Reviews: