Trident Series PD765 Process & Temperature Meters
Instruction Manual
21
Main Menu
The main menu consists of the most commonly used
functions:
Setup
and
Password
.
•
Press
Menu
button to enter Programming Mode
then press
Up
arrow button to scroll main menu.
•
Press
Menu
, at any time, to exit and return to
Run Mode. Changes made to settings prior to
pressing
Enter/Ack
are not saved.
•
Changes to the settings are saved to memory
only after pressing
Enter/Ack
.
•
The display moves to the next menu every time a
setting is accepted by pressing
Enter/Ack
.
Setting Numeric Values
The numeric values are set using the
Right
and
Up
arrow buttons. Press
Right
arrow to select next digit
and
Up
arrow to increment digit value.
The digit being changed is displayed brighter than the
rest.
Press the
Enter/Ack
button, at any time, to accept a
setting or
Menu
button to exit without saving changes.
The decimal point is set using the
Up
arrow button in
the
Setup-decimal point
menu.
Setting Up the Meter (
setu
)
The
Setup
menu is used to select:
1. Input signal the meter will accept
2. Decimal point position for process inputs
3. Units (
°
F or
°
C) for temperature inputs
4. Relay operation
5. 4-20 mA analog output setup
Press the
Enter/Ack
button to access any menu or
press
Up
arrow button to scroll through choices.
Press the
Menu
button to exit at any time.
Notes:
1. Selecting RTD or TC mode from the Input menu will include
the Fahrenheit/Celsius menu in the setup menu structure.
RTD will allow the selection of a decimal point location after
this menu and TC has a fixed decimal point location and will
not allow the selection of a decimal point location.
2. Relay menu is always available even if relays option is not
installed. Visual alarm indication is available through front
panel LEDs and MeterView software.
3. Analog Output menu is available if selected in the Advanced
Features menu. 4-20 mA output option board is installed and
set up at the factory.
Setting the Input Signal (
inpt
)
Enter the
Input
menu to set up the meter to display
current (
4-20
), voltage (
0-10
), thermocouple (
tC
), or
RTD (
rtd
) inputs.
The voltage input is capable of accepting any signal
from -10 to +10 VDC. Select voltage input to accept
0-5, 1-5, 0-10, or
±
10 VDC signals.
The current input is capable of accepting any signal
from -20 to 20 mA. Select current input to accept 0-20
or 4-20 mA signals.