Trident Series PD765 Process & Temperature Meters
Instruction Manual
10
MOD-LH Light / Horn
Available for
these Models
Trident X2 only.
Light Colors
MOD-LH Models: Red, green, yellow,
blue or white.
MOD-LH5CB1: User selectable: red,
green, yellow, blue, or white.
Light Action
Can be wired to flash (not available on
MOD-LH5CB1) or stay steady on
Light / Horn &
Reset Button
Installation
When MOD-LH is ordered with an en-
closure, the user performs installation
and wiring of Light / Horn and Reset
Button in predrilled holes.
Horn
85 dB
Rating
IP65
Light / Horn
Independence
Light and horn can be
controlled via separate relays
Power
Requirement
No additional power required when
wired to a Trident X2 meter. When
mounted remote: 24 VDC
Transmitter
Power Supply
The Trident X2's internal transmitter
power supply is capable of supplying
24 VDC @ 200 mA to power the
transmitter and other devices such as
the Light / Horn. The following table
illustrates how much of this current is
required to drive various Light / Horns.
If more current is needed, then
consider the PDA1024-01.
MOD-LH and MOD-LH5CB1-X2 Models:
Color Current Required
Color Current Required
Red
17 mA
Blue
15 mA
Green 15 mA
White 42 mA
Yellow 23 mA
Horn
20 mA
Example:
17 mA (Red Light) + 20 mA (Horn) = 37 mA total
current needed from the 200 mA supply. Available current =
163 mA
Reset / Silence
Button
NEMA 4X; may be wired to the
external button contacts on Trident X2.
The Ack front panel button can be used
to reset / acknowledge the relays.
Reset Button
Labels
The Light / Horn accessory comes with
9 pre-printed message labels the user
can affix under the red button: RESET,
BATCH, ACK, TARE, SILENCE, STOP,
START, PAUSE, START/STOP.
Light / Horn
Mounting
Connection
M22
Hole Sizes
Light / Horn: 0.875" (22 mm)
Reset Button
0.630" (16 mm)
Cable Length
3.28 feet (1 meter)
Operating
Temperature
Range
-5 to 40°C (23 to 104°F)
Compliance Information
Safety
Ul Listed
USA and Canada
UL 508 Industrial Control Equipment
Ul File Number
E160849
Front Panel
UL Type 4X, NEMA 4X, IP65; panel
gasket provided
Low Voltage
Directive
EN 61010-1:2010
Safety requirements for measurement,
control, and laboratory use
Electromagnetic Compatibility
Emissions
EN 55011:2009 + A1:2010
Group 1 Class A ISM emissions
requirements
Radiated
Emissions
Class A
AC Mains
Conducted
Emissions
Class A
Immunity
EN 61326-1:2013
Measurement, control, and laboratory
equipment
EN 61000-6-2:2005
EMC heavy industrial generic immunity
standard
RFI -
Amplitude
Modulated
80 -1000 MHz 10 V/m 80% AM (1 kHz)
1.4 - 2.0 GHz 3 V/m 80% AM (1 kHz)
2.0 - 2.7 GHz 1 V/m 80% AM (1 kHz)
Electrical Fast
Transients
±2kV AC mains, ±1kV other
Electrostatic
Discharge
±4kV contact, ±8kV air
RFI -
Conducted
10V, 0.15-80 MHz, 1kHz 80% AM
AC Surge
±2kV Common, ±1kV Differential
Surge
1KV (CM)
Power-
Frequency
Magnetic Field
30 A/m 70%V for 0.5 period
Voltage Dips 40%V for 5 & 50 periods
70%V for 25 periods
Voltage
Interruptions
<5%V for 250 periods
Note:
Testing was conducted on meters installed through the
covers of grounded metal enclosures with cable shields
grounded at the point of entry representing installations
designed to optimize EMC performance.
Declaration of Conformity available at