Sabre P PD603 Low-Cost Process Meter
Instruction Manual
7
Connections
All connections are made to removable screw
terminal connectors located at the rear of the meter.
Use copper wire with 60°C or 60/75°C insulation
for all line voltage connections. Observe all safety
regulations. Electrical wiring should be performed
in accordance with all applicable national, state,
and local codes to prevent damage to the meter
and ensure personnel safety.
Connector Labeling
The connectors label, affixed to the meter, shows the
location of the connectors available with requested
configuration.
Figure 4. Connector Labeling - No Options
Figure 5. Connector Labeling - Meter with 24 V
Supply
Power Connections
Power connections are made to a two-terminal
connector labeled POWER on Figure 4. The meter will
operate regardless of DC polarity connection. The +
and - symbols are only a suggested wiring convention.
Figure 6. Power Connections
Signal Connections
Signal connections are made to a five-terminal
connector labeled SIGNAL on Figure 4. The COM
(common) terminal is the return for all types of input
signals.
Current and Voltage Connections
The following figures show examples for current and
voltage connections.
There are no switches or jumpers to set up for current
and voltage inputs. Setup and programming is
performed through the front panel buttons.
Figure 7. Transmitter Powered by External Supply
or Self-Powered
Figure 8. Transmitters Powered by Internal Supply
(Optional)
The current input is protected against current
overload by a resettable fuse. The display may or
may not show a fault condition depending on the
nature of the overload.
The fuse limits the current to a safe level when it
detects a fault condition, and automatically resets
itself when the fault condition is removed.
Figure 9. Voltage Input Connections
The meter is capable of accepting any voltage from
-10 VDC to +10 VDC.
1
2
AC or DC
POWER
Required External Fuse:
5 A max, Slow Blow
POWER CONNECTOR
+
-
COM
mA+
2
1
3
5
4
V+
X
X
External
Power
Supply
2-Wire
4-20 mA
Transmitter
-
+
+ -
SIGNAL CONNECTOR
COM
SIGNAL CONNECTOR
mA+
2
1
3
5
4
V+
X
X
2-Wire 4-20 mA
Self-Powered
Transmitter
-
+
COM
SIGNAL CONNECTOR
mA+
2
1
3
5
4
V+
X
X
2-Wire
4-20 mA
Transmitter
-
+
P+
P-
2
1
24V OUT
COM
SIGNAL CONNECTOR
mA+
2
1
3
5
4
V+
X
X
3-Wire
4-20 mA
Transmitter
Signal
+
2
1
24V OUT
-
P+
P-
SIGNAL CONNECTOR
2
1
3
5
4
Voltage
Signal
+ -
COM
mA+
V+
X
X
COM
SIGNAL CONNECTOR
mA+
2
1
3
5
4
V+
X
X
3-Wire
Voltage
Transducer
Signal
+
2
1
24V OUT
-
P+
P-