Sabre P PD603 Low-Cost Process Meter
Instruction Manual
6
INSTALLATION
There is no need to remove the meter from its case to
complete the installation, wiring, and setup of the
meter.
Unpacking
Remove the meter from box. Inspect the packaging
and contents for damage. Report damages, if any, to
the carrier.
If any part is missing or the meter malfunctions,
please contact your supplier or the factory for
assistance.
Panel Mounting
•
Prepare a standard 1/8 DIN panel cutout –
3.622" x 1.772" (92 mm x 45 mm). Refer to
Mounting Dimensions
on page 6 for more details.
•
Clearance: allow at least 4" (102 mm) behind the
panel for wiring.
•
Panel thickness: 0.04" - 0.25" (1.0 mm - 6.4 mm).
Recommended minimum panel thickness to
maintain Type 4X rating: 0.06" (1.5 mm) steel
panel, 0.16" (4.1 mm) plastic panel.
•
Remove the two mounting brackets provided with
the meter (back-off the two screws so that there is
¼" (6.4 mm) or less through the bracket. Slide the
bracket toward the front of the case and remove).
•
Insert meter into the panel cutout.
•
Install mounting brackets and tighten the screws
against the panel. To achieve a proper seal,
tighten the mounting bracket screws evenly until
meter is snug to the panel along its short side.
DO NOT OVER TIGHTEN, as the rear of the
panel may be damaged.
Figure 1. Panel Cutout and Mounting
MOUNTING DIMENSIONS
Figure 2. Meter Dimensions - Side View
Figure 3. Case Dimensions - Top View
1.76"
(45mm)
0.59"
(15mm)
3.2"
(81mm)
2.45"
(62mm)
3.6"
(91mm)