Sabre P PD603 Low-Cost Process Meter
Instruction Manual
5
COMPLIANCE INFORMATION
Safety
UL LISTED
USA and Canada
UL 508 Industrial Control Equipment
UL FILE NUMBER
E160849
FRONT PANEL
UL Type 4X, NEMA 4X, IP65; panel
gasket provided
LOW VOLTAGE
DIRECTIVE
EN 61010-1:2010
Safety requirements for measurement,
control, and laboratory use
Electromagnetic Compatibility
EMISSIONS
EN 55011:2009+Al:2010
Group 1 Class A ISM emissions
requirements
Radiated
Emissions
Class A
AC Mains
Conducted
Emissions
Class A
IMMUNITY
EN 61326-1:2013
Measurement, control, and laboratory
equipment
EN 61000-6-2:2005
EMC heavy industrial generic immunity
standard
RFI -
Amplitude
Modulated
80 -1000 MHz 10 V/m 80% AM (1 kHz)
1.4 - 2.0 GHz 3 V/m 80% AM (1 kHz)
2.0 - 2.7 GHz 1 V/m 80% AM (1 kHz)
Electrical
Fast
Transients
±2kV AC mains, ±1kV other
Electrostatic
Discharge
±4kV contact, ±8kV air
RFI -
Conducted
10V, 0.15-80 MHz, 1kHz 80% AM
AC Surge
±2kV Common, ±1kV Differential
Surge
1KV (CM)
Power-
Frequency
Magnetic
Field
30 A/m 70%V for 0.5 period
Voltage Dips
40%V for 5 & 50 periods
70%V for 25 periods
Voltage
Interruptions
<5%V for 250 periods
Note:
Testing was conducted on PD603 meters installed
through the covers of grounded metal enclosures
with cable shields grounded at the point of entry
representing installations designed to optimize
EMC performance.
SAFETY INFORMATION
CAUTION
: Read
complete instructions
prior to installation
and operation of the
meter.
WARNING
: Risk of
electric shock.
WARNING
Hazardous voltages exist within enclosure.
Installation and service should be performed only
by trained service personnel.
!