Precision Digital Corporation Sabre P PD603 Instruction Manual Download Page 11

Sabre P PD603 Low-Cost Process Meter 

Instruction Manual 

 

11

 

Setting Up the Password (

pass

The 

Password

 menu is used to program a four-digit 

password to prevent unauthorized changes to the 
programmed parameter settings. 

Locking the Meter 

Enter the 

Password

 menu and program a four-digit 

password. 
For instructions on how to program numeric values 
see 

Setting Numeric Values

, page 9.  

 

Record the password for future reference. If 
appropriate, it may be recorded in the space provided. 

Model:  

 

Serial Number:   
Password:  

__  __  __  __ 

Unlocking the Meter 

If the meter is password protected, the correct 
password must be entered in order to make changes 
to the parameter settings. 

 

Entering the correct four-digit number sets the 
password to 0000, disabling the protection. 
Changes to the programmed parameter settings are 
allowed only with the password set to 0000. 
If the password entered is incorrect, the meter 
displays 

LoCd

 (Locked) for about two seconds, then it 

returns to Run Mode. To try again, press 

Enter/Ack

 

while the 

Locked

 message is displayed. 

 

Forgot the Password? 

The password may be disabled by the following  
procedure: 
1. 

Note display reading prior to pressing the Menu 
button. Ignore decimal point and sign. 

2. 

Access the 

Password

 menu, add 2 to the noted 

reading and enter that number as the password 
(e.g. display reading = -1.23, password = 0125). 

 

OPERATION 

For process inputs, the meter is capable of accepting 
positive and negative signals and displaying these 
signals in engineering units from -1999 to 9999 (

e.g.

 a 

signal from -10 to +10 VDC could be displayed as -1000 
to 1000). 

Front Panel Buttons Operation 

Button 

Symbol 

Description 

 

Press to enter or exit 
Programming Mode, view 
settings, or exit Max/Min 
readings 

 

Press to reset Max/Min readings 

 

Press to display Max/Min 
readings alternately 

 

Press to display Max/Min reading 
indefinitely while displaying 
Max/Min 

 

Maximum/Minimum Readings 

The main function of the front panel buttons during 
operation is to display the maximum and minimum 
readings reached by the process. 

 

1.  Press 

Up 

arrow/

Max

 button to display maximum 

reading since the last reset/power-up. 

2.  Press 

Up 

arrow/

Max

 again to display the 

minimum reading since the last reset/power-up. 

3.  Press 

Enter/Ack 

to hold Max/Min display 

reading, the meter will continue to track new 
Max/Min readings. 

4.  If 

Enter/Ack 

is not pressed, the Max/Min display 

reading will time out after ten seconds and the 
meter will return to display the actual reading. 

5.  Press 

Right 

arrow/

Reset

 button to reset Max/Min 

while reading is being displayed. Max/Min display 
readings are reset to actual  
reading. 

Summary of Contents for Sabre P PD603

Page 1: ...20 mA 0 5 1 5 0 10 10 V Inputs 4 Digit Display 0 56 14 2 mm Shallow Depth Case Extends Only 3 6 91 mm Behind Panel Isolated 24 VDC 200 mA Transmitter Power Supply Option No Assembly Required Operating Temperature Range 0 to 65 C 32 to 150 F UL C UL Listed E160849 508 Industrial Control Equipment Input Power Options 85 265 VAC or 12 36 VDC Max Min Display Easy Front Panel Programming No Jumpers Swi...

Page 2: ...VDC power supply for the transmitter The meter is easily programmed and scaled with its four front panel buttons and simple menu structure ORDERING INFORMATION 85 265 VAC Model 12 36 VDC Model Description PD603 6R0 0 PD603 7R0 0 Process Meter PD603 6R0 1 Process Meter with 24 V transmitter supply All models may be powered from AC or DC see Specifications for details Quick Shipment Program product ...

Page 3: ...ing the Decimal Point dec p 9 Programming the Meter prog 10 Scaling the Meter ScAL 10 Calibrating the Meter Cal 10 Setting Up the Password pass 11 Locking the Meter 11 Unlocking the Meter 11 OPERATION 11 Front Panel Buttons Operation 11 Maximum Minimum Readings 11 TROUBLESHOOTING 12 Troubleshooting Tips 12 QUICK USER INTERFACE REFERENCE GUIDE 12 EU DECLARATION OF CONFORMITY 13 Table of Figures Fig...

Page 4: ...I Local level with smaller transient overvoltages than Installation Overvoltage Category III ENVIRONMENTAL Operating temperature range 0 to 65 C 32 to 150 F Storage temperature range 40 to 85 C 40 to 185 F Relative humidity 0 to 90 non condensing CONNECTIONS Removable screw terminal blocks accept 12 to 22 AWG wire RJ11 for factory use only ENCLOSURE 1 8 DIN high impact plastic UL 94V 0 color gray ...

Page 5: ... 1 kHz 1 4 2 0 GHz 3 V m 80 AM 1 kHz 2 0 2 7 GHz 1 V m 80 AM 1 kHz Electrical Fast Transients 2kV AC mains 1kV other Electrostatic Discharge 4kV contact 8kV air RFI Conducted 10V 0 15 80 MHz 1kHz 80 AM AC Surge 2kV Common 1kV Differential Surge 1KV CM Power Frequency Magnetic Field 30 A m 70 V for 0 5 period Voltage Dips 40 V for 5 50 periods 70 V for 25 periods Voltage Interruptions 5 V for 250 p...

Page 6: ...ring Panel thickness 0 04 0 25 1 0 mm 6 4 mm Recommended minimum panel thickness to maintain Type 4X rating 0 06 1 5 mm steel panel 0 16 4 1 mm plastic panel Remove the two mounting brackets provided with the meter back off the two screws so that there is 6 4 mm or less through the bracket Slide the bracket toward the front of the case and remove Insert meter into the panel cutout Install mounting...

Page 7: ... The following figures show examples for current and voltage connections There are no switches or jumpers to set up for current and voltage inputs Setup and programming is performed through the front panel buttons Figure 7 Transmitter Powered by External Supply or Self Powered Figure 8 Transmitters Powered by Internal Supply Optional The current input is protected against current overload by a res...

Page 8: ...access a menu or to accept a setting Display Functions and Messages The meter displays various functions and messages during setup programming and operation The following table shows the displayed functions and messages with their action setting description Display Parameter Action Setting setu4 Setup Enter Setup menu inpt4 Input Enter Input menu 4 204 4 20 mA Set meter for 4 20 mA input 0 104 0 1...

Page 9: ...t without saving changes The decimal point is set using the Up arrow button in the Setup decimal point menu Setting Up the Meter setu The Setup menu is used to select 1 Input signal the meter will accept 2 Decimal point position 3 Program Press the Enter Ack button to access any menu or press Up arrow button to scroll through choices Press the Menu button to exit at any time Setting the Input Sign...

Page 10: ... An error message indicates that the calibration or scaling process was not successful After the error message is displayed the meter reverts to input 1 allowing the appropriate input signals to be applied The error message might be caused by any of the following conditions 1 Input signal is not connected to the proper terminals or it is connected backwards 2 Wrong signal selection in Setup menu 3...

Page 11: ... point and sign 2 Access the Password menu add 2 to the noted reading and enter that number as the password e g display reading 1 23 password 0125 OPERATION For process inputs the meter is capable of accepting positive and negative signals and displaying these signals in engineering units from 1999 to 9999 e g a signal from 10 to 10 VDC could be displayed as 1000 to 1000 Front Panel Buttons Operat...

Page 12: ...t four digit password to unlock Meter displays error message during calibration err Check 1 Signal connections 2 Input selected in Setup menu 3 Minimum input span requirements Meter displays 99994 4 19994 Check 1 Input selected in Setup menu 2 Corresponding signal at Signal connector Display alternates between 1 Hi and a number 2 Lo and a number Press Menu to exit Max Min display readings If the d...

Page 13: ...cal standards and when applicable or required a European Union notified body certification Standards EN 55011 1998 EN 61000 6 2 2001 EN 61010 1 1995 EN 61326 2006 The standards EN 55011 1998 EN 61000 6 2 2001 EN 61010 1 1995 and EN 61326 2006 are no longer harmonized The requirements of these standards have been checked against the harmonized standards EN 55011 2009 A1 2010 EN 61000 6 2 2005 EN 61...

Page 14: ...0 www predig com LIM603_F SFT031 Ver 3 2 up 02 20 Contact Precision Digital Technical Support Call 800 610 5239 or 508 655 7300 Fax 508 655 8990 Email support predig com Sales Support Call 800 343 1001 or 508 655 7300 Fax 508 655 8990 Email sales predig com Place Orders Email orders predig com For the latest version of this manual please visit www predig com ...

Reviews: