Sabre P PD603 Low-Cost Process Meter 

Instruction Manual

 

 

PRECISION DIGITAL CORPORATION

 

 

233 South Street • Hopkinton MA 01748 USA 
Tel (800) 343-1001 • Fax (508) 655-8990 

www.predig.com 

 

 

 

 

 

  1/8 DIN Digital Panel Meter with NEMA 4X, IP65 Front 

  0-20, 4-20 mA, 0-5, 1-5, 0-10, ±10 V Inputs 

  4-Digit Display, 0.56" (14.2 mm) 

  Shallow Depth Case Extends Only 3.6" (91 mm) Behind Panel 

  Isolated 24 VDC @ 200 mA Transmitter Power Supply Option 

  No Assembly Required 

  Operating Temperature Range: 0 to 65°C (32 to 150°F) 

  UL & C-UL Listed. E160849; 508 Industrial Control Equipment 

  Input Power Options: 85-265 VAC or 12-36 VDC 

  Max/Min Display 

  Easy Front Panel Programming; No Jumpers, Switches or Solder Pads 

  1-Year Warranty 

 

Summary of Contents for Sabre P PD603

Page 1: ...20 mA 0 5 1 5 0 10 10 V Inputs 4 Digit Display 0 56 14 2 mm Shallow Depth Case Extends Only 3 6 91 mm Behind Panel Isolated 24 VDC 200 mA Transmitter Power Supply Option No Assembly Required Operating Temperature Range 0 to 65 C 32 to 150 F UL C UL Listed E160849 508 Industrial Control Equipment Input Power Options 85 265 VAC or 12 36 VDC Max Min Display Easy Front Panel Programming No Jumpers Swi...

Page 2: ...VDC power supply for the transmitter The meter is easily programmed and scaled with its four front panel buttons and simple menu structure ORDERING INFORMATION 85 265 VAC Model 12 36 VDC Model Description PD603 6R0 0 PD603 7R0 0 Process Meter PD603 6R0 1 Process Meter with 24 V transmitter supply All models may be powered from AC or DC see Specifications for details Quick Shipment Program product ...

Page 3: ...ing the Decimal Point dec p 9 Programming the Meter prog 10 Scaling the Meter ScAL 10 Calibrating the Meter Cal 10 Setting Up the Password pass 11 Locking the Meter 11 Unlocking the Meter 11 OPERATION 11 Front Panel Buttons Operation 11 Maximum Minimum Readings 11 TROUBLESHOOTING 12 Troubleshooting Tips 12 QUICK USER INTERFACE REFERENCE GUIDE 12 EU DECLARATION OF CONFORMITY 13 Table of Figures Fig...

Page 4: ...I Local level with smaller transient overvoltages than Installation Overvoltage Category III ENVIRONMENTAL Operating temperature range 0 to 65 C 32 to 150 F Storage temperature range 40 to 85 C 40 to 185 F Relative humidity 0 to 90 non condensing CONNECTIONS Removable screw terminal blocks accept 12 to 22 AWG wire RJ11 for factory use only ENCLOSURE 1 8 DIN high impact plastic UL 94V 0 color gray ...

Page 5: ... 1 kHz 1 4 2 0 GHz 3 V m 80 AM 1 kHz 2 0 2 7 GHz 1 V m 80 AM 1 kHz Electrical Fast Transients 2kV AC mains 1kV other Electrostatic Discharge 4kV contact 8kV air RFI Conducted 10V 0 15 80 MHz 1kHz 80 AM AC Surge 2kV Common 1kV Differential Surge 1KV CM Power Frequency Magnetic Field 30 A m 70 V for 0 5 period Voltage Dips 40 V for 5 50 periods 70 V for 25 periods Voltage Interruptions 5 V for 250 p...

Page 6: ...ring Panel thickness 0 04 0 25 1 0 mm 6 4 mm Recommended minimum panel thickness to maintain Type 4X rating 0 06 1 5 mm steel panel 0 16 4 1 mm plastic panel Remove the two mounting brackets provided with the meter back off the two screws so that there is 6 4 mm or less through the bracket Slide the bracket toward the front of the case and remove Insert meter into the panel cutout Install mounting...

Page 7: ... The following figures show examples for current and voltage connections There are no switches or jumpers to set up for current and voltage inputs Setup and programming is performed through the front panel buttons Figure 7 Transmitter Powered by External Supply or Self Powered Figure 8 Transmitters Powered by Internal Supply Optional The current input is protected against current overload by a res...

Page 8: ...access a menu or to accept a setting Display Functions and Messages The meter displays various functions and messages during setup programming and operation The following table shows the displayed functions and messages with their action setting description Display Parameter Action Setting setu4 Setup Enter Setup menu inpt4 Input Enter Input menu 4 204 4 20 mA Set meter for 4 20 mA input 0 104 0 1...

Page 9: ...t without saving changes The decimal point is set using the Up arrow button in the Setup decimal point menu Setting Up the Meter setu The Setup menu is used to select 1 Input signal the meter will accept 2 Decimal point position 3 Program Press the Enter Ack button to access any menu or press Up arrow button to scroll through choices Press the Menu button to exit at any time Setting the Input Sign...

Page 10: ... An error message indicates that the calibration or scaling process was not successful After the error message is displayed the meter reverts to input 1 allowing the appropriate input signals to be applied The error message might be caused by any of the following conditions 1 Input signal is not connected to the proper terminals or it is connected backwards 2 Wrong signal selection in Setup menu 3...

Page 11: ... point and sign 2 Access the Password menu add 2 to the noted reading and enter that number as the password e g display reading 1 23 password 0125 OPERATION For process inputs the meter is capable of accepting positive and negative signals and displaying these signals in engineering units from 1999 to 9999 e g a signal from 10 to 10 VDC could be displayed as 1000 to 1000 Front Panel Buttons Operat...

Page 12: ...t four digit password to unlock Meter displays error message during calibration err Check 1 Signal connections 2 Input selected in Setup menu 3 Minimum input span requirements Meter displays 99994 4 19994 Check 1 Input selected in Setup menu 2 Corresponding signal at Signal connector Display alternates between 1 Hi and a number 2 Lo and a number Press Menu to exit Max Min display readings If the d...

Page 13: ...cal standards and when applicable or required a European Union notified body certification Standards EN 55011 1998 EN 61000 6 2 2001 EN 61010 1 1995 EN 61326 2006 The standards EN 55011 1998 EN 61000 6 2 2001 EN 61010 1 1995 and EN 61326 2006 are no longer harmonized The requirements of these standards have been checked against the harmonized standards EN 55011 2009 A1 2010 EN 61000 6 2 2005 EN 61...

Page 14: ...0 www predig com LIM603_F SFT031 Ver 3 2 up 02 20 Contact Precision Digital Technical Support Call 800 610 5239 or 508 655 7300 Fax 508 655 8990 Email support predig com Sales Support Call 800 343 1001 or 508 655 7300 Fax 508 655 8990 Email sales predig com Place Orders Email orders predig com For the latest version of this manual please visit www predig com ...