Model PD6363 Pulse Dual-Input Rate/Totalizer Instruction Manual
53
Setting the Relay Operation (
relay
)
This menu is used to set up the assignment and operation of the relays.
Caution!
During setup, the relays do not follow the input and
they will remain in the state found prior to entering
the Relay menu.
1. Relay
assignment
a. Channel A rate, total, or grand total
b. Channel B rate, total, or grand total
c. Channel C (Math channel)
d. Modbus
2. Relay
action
a. Automatic reset only (non-latching)
b. Aut manual reset at any time (non-latching)
c. Latching (manual reset only)
d. Latching with Clear (manual reset only after alarm
condition has cleared)
e. Pump alternation control (automatic reset only)
f.
Sampling (the relay is activated for a user-specified time)
g. Off (relay state controlled by Interlock feature)
3. Set
point
4. Reset
point
5. Fail-safe
operation
a. On
(enabled)
b. Off
(disabled)
6. Time
delay
a. On delay (0-999.9 seconds)
b. Off delay (0-999.9 seconds)
!