Model PD6363 Pulse Dual-Input Rate/Totalizer Instruction Manual
50
Totalizer Setup (
tsetup
)
The time base and total and grand total conversion factors for input
channels A and B are located in the
Totalizer Setup
menu.
The time base is determined by the rate programming. Enter the time
unit of the programmed rate scale.
For example: A rate display scaled in
engineering units of gallons per minute would use a time base of
minutes.
Total & grand total conversion factors for channel A and B are
programmed independently. This means that one total or grand total
can be displaying the value in gallons while another displays in million
gallons, liters, m
3
, etc.
Total & Grand Total Reset (
treset
)
Total reset menus are located in the
Program
menu. The totals can be
programmed for manual or automatic reset. In the automatic reset
mode, a programmable time delay (
t dly
) in seconds is available to
reset the total or grand total after the assigned preset is reached.