36
Maintained Alarm
(
ACK
before
RESET
)
Condition
LED
Horn
1
st
Pt
Next Pt
Normal
Off Off
Off
Alert
Intermittent Flash
Fast Flash
On
ACK
Pushbutton
Acknowledge
Slow Flash
Steady
Off
RESET
Pushbutton
1
st
Out Reset
Steady Steady
Off
Normal
Off Off
Off
Sequence F3A Flowchart Sequence F3A
Switch Positions
Reset
Pressed
Condition
Normal
1
st
Pt LED
Off
Next Pt LED
Off
Horn
Off
Condition
Alert
1
st
Pt LED
Intermittent Flash
Next Pt LED
Fast Flash
Horn
On
Alarm Condition
Ack while
Normal
Reset
Pressed
Condition
Any
1
st
Pt LED
Fast Flash
Next Pt LED
Fast Flash
Horn
On
Ack while
Normal
Condition
Alert
1
st
Pt LED
Steady
Next Pt LED
Steady
Horn
Off
Condition
Normal
1
st
Pt LED
Slow Flash
Next Pt LED
Off
Horn
Off
Condition
Alert
1
st
Pt LED
Slow Flash
Next Pt LED
Steady
Horn
Off
Ack while
Alarmed
Ack while
Alarmed
Return
to Normal
Return
to Normal