PD154 & PD158 Vigilante
®
II Annunciators
Instruction Manual
32
ISA Sequence A
Acknowledge Pushbutton and Automatic Reset
Momentary Alarm
Maintained Alarm
Sequence
A
Sequence
A
Flowchart
Switch Positions
Condition
LED
Horn
Condition
LED
Horn
Normal
Off Off
Normal
Off Off
Alert
Flash On
Alert
Flash
On
Normal
Flash On
ACK
Pushbutton
ACK
Pushbutton
Acknowledge
Steady
Off
Acknowledge
Off Off
Normal
Off Off
Condition
Normal
LED
Off
Horn
Off
Condition
Alert
LED
Flash
Horn
On
Condition
Alert
LED
Steady
Horn
Off
Alarm Condition
Ack when
Inputs Normal
Return
to Normal
Ack
Pressed
Relay Operation
For complete details on relay function, see page 24.
Relay 1: Operation
Relay 1 enters alarm state when there is a new alarm. This relay will clear
when the alarms are acknowledged.
Relay 2 Operation
Relay 2 enters alarm state when any channel displays in alarm state. This
relay will clear when all indication LEDs are cleared.