Helios PD2-6080/PD2-6081 Modbus
®
Scanners
Instruction Manual
44
Setting the Relay Operation (
relay
)
This menu is used to set up the assignment and operation of the relays.
Relay Setup Menu (
relay setup
)
• During setup, the relays do not follow the input and
they will remain in the state found prior to entering
the Relay menu.
1.
Assign
Relay assignment
a. Assign relay to PV
b. Assign relay to Math channel
c.
Assign relay to multiple PVs
(2 to 16 PVs)
2.
Act 1
Relay action
a. Automatic reset only (non-latching)
b. Aut manual reset at any time
(non-latching)
c.
Latching (manual reset only)
d. Latching with Clear (manual reset only
after alarm condition has cleared)
e. Pump alternation control (automatic
reset only)
f.
Sampling (the relay is activated for a
user-specified time)
g. Off (relay state controlled by Interlock
feature)
3.
Set 1
Set point &
Rst 1
Reset point
4.
Failsf
Fail-safe operation
a. On (enabled)
b. Off (disabled)
5.
Delay
Time delay
a. On delay (0-999.9 seconds)
b. Off delay (0-999.9 seconds)
6.
Break
Relay action for communications
break or loss of 4-20 mA input