background image

6335V109-IN

 

7

Tc inputs:

Cold junction compensation .......................  < ±1.0°C
External CJC with Ni100 or Pt100 ..............  -40 

 Tamb. 

 135°C

Sensor error detection ................................  Yes
Sensor error current: 
 

When detecting ....................................  Nom. 33 

m

A

 

Else.......................................................  0 

m

A

Short circuit detection .................................  If 0% > 5 mV

voltage inputs:

Measurement range  ...................................  -800...+800 mV

Min. span .....................................................  2.5 mV

Input resistance ...........................................  10 M

Ω

current output:

Signal range ................................................  4...20 mA 

Min. signal range .........................................  16 mA

Updating time ..............................................  440 ms

 

(660 ms for diff.)

Fixed output signal ......................................  Between 4 and 20 mA

Output signal at EEprom error .................... 

≤ 

3.5 mA

Load resistance ........................................... 

≤ 

(V

supply

 - 8) / 0.023 

[Ω ]

Load stability ...............................................  < ±0.01% of span / 100 

Ω

Sensor error detection:

Programmable .............................................  3.5...23 mA

NAMUR NE43 Upscale ...............................  23 mA

NAMUR NE43 Downscale ...........................  3.5 mA

Of span = Of the presently selected range

 

Type

Min. 

temperature

Max. 

temperature

Min. 

span

 

Standard

W3 

W5

+400°C 

-100°C 

-100°C 

-180°C 

-100°C 

-180°C 

-50°C 

-50°C 

-200°C 

-200°C 

0°C 

0°C

+1820°C 

+1000°C 

+1200°C 

+1372°C 

+900°C 

+1300°C 

+1760°C 

+1760°C 

+400°C 

+600°C 

+2300°C 

+2300°C

100°C 

50°C 

50°C 

50°C 

50°C 

50°C 

100°C 

100°C 

50°C 

50°C 

100°C 

100°C

IEC584 

IEC584 

IEC584 

IEC584 

DIN 43710 

IEC584 

IEC584 

IEC584 

IEC584 

DIN 43710 

ASTM E988-90 

ASTM E988-90

CONTENTS

Summary of Contents for PRetrans 6335

Page 1: ...S I G N A L S T H E B E S T 6 3 3 5 2 W i r e H A R T T r a n s m i t t e r N o 6 3 3 5 V 1 0 9 I N F r o m s e r n o 1 0 0 9 2 4 0 0 0 DK UK FR DE ES RU ...

Page 2: ... electronics A S offre une large gamme de produits pour le traite ment des signaux analogiques et numériques dans tous les domaines industriels La gamme de produits s étend des transmetteurs de température aux afficheurs des isolateurs aux interfaces SI jusqu aux modules universels Vous pouvez compter sur nos produits même dans les conditions d utilisation sévères p ex bruit électrique vibrations ...

Page 3: ...tion 3 Applications 4 Order 6335 5 Electrical specifications 5 Connections 9 Block diagram 11 Programming 12 Connection of transmitters in multidrop mode 14 Appendix 15 ATEX Installation Drawing 6335A 15 ATEX Installation Drawing 6335D 15 IECEx installation drawing 6335D 15 FM Installation Drawing No 6335QF01 15 CSA Installation Drawing No 6335QC02 15 ...

Page 4: ...61326 1 2006 For specification of the acceptable EMC performance level refer to the electrical specifications for the module The ATEX Directive 94 9 EC and later amendments EN 60079 0 2006 EN 60079 11 2007 EN 60079 15 2005 and EN 60079 26 2007 ATEX certificate KEMA 10ATEX0006 X 6335A ATEX certificate KEMA 09ATEX0148 6335D Notified body KEMA Quality B V 0344 Utrechtseweg 310 6812 AR Arnhem P O Box ...

Page 5: ...ignal with HART communication Technical characteristics Within a few seconds the user can program PR6335 to measure temperatures within all ranges defined by the norms The RTD and resistance inputs have cable compensation for 2 3 and 4 wire connection The 6335 has been designed according to strict safety requirements and is thus suitable for application in SIL 2 installations A limit can be progra...

Page 6: ... mA TC to 4 20 mA Resistance to 4 20 mA Difference or average RTD TC or mV 2 wire installation in control room 2 wire installation in control room 2 wire installation in control room 2 wire installation in control room mV to 4 20 mA 2 wire installation in control room CONTENTS ...

Page 7: ... channel 2 Standard 3 75 kVAC CSA FM ATEX IECEx 1500 VAC Warm up time 30 s Communications interface Loop Link and HART Signal noise ratio Min 60 dB Response time programmable 1 60 s EEprom error check 10 s Signal dynamics input 22 bit Signal dynamics output 16 bit Calibration temperature 20 28 C Accuracy the greater of general and basic values Order 6335 General values Input type Absolute accuracy...

Page 8: ...mA Effect of sensor cable resistance 3 4 wire 0 002 Ω Ω Sensor error detection Yes Short circuit detection If 0 30 Ω RTD type Min value Max value Min span Standard Pt100 Ni100 Lin R 200 C 60 C 0 W 850 C 250 C 7000 W 10 C 10 C 10 W IEC 60751 DIN 43760 Basic values Input type Basic accuracy Temperature coefficient Pt100 and Pt1000 0 1 C 0 005 C C Ni100 0 2 C 0 005 C C Lin R 0 1 Ω 5 mW C Volt 10 µV 0...

Page 9: ...put signal at EEprom error 3 5 mA Load resistance Vsupply 8 0 023 Ω Load stability 0 01 of span 100 Ω Sensor error detection Programmable 3 5 23 mA Namur NE43 Upscale 23 mA Namur NE43 Downscale 3 5 mA Of span Of the presently selected range Type Min temperature Max temperature Min span Standard B E J K L N R S T U W3 W5 400 C 100 C 100 C 180 C 100 C 180 C 50 C 50 C 200 C 200 C 0 C 0 C 1820 C 1000 ...

Page 10: ...QA01 IECEx KEM 10 0084 Ex ia IIC T5 Ga IECEx Installation Drawing No 6335QI01 FM applicable in IS Class I Div 1 Group A B C D IS Class I Zone 0 AEx ia IIC FM Installation Drawing No 6335QF01 CSA applicable in IS Class I Div 1 Group A B C D Ex ia IIC IS Class I Zone 0 AEx ia IIC CSA Installation Drawing No 6335QC02 GOST R approval VNIIM VNIIFTRI Cert no See www prelectronics com Observed authority ...

Page 11: ...3 51 52 54 53 51 52 54 53 51 52 54 53 51 54 CJC 52 41 42 44 CJC Channel 1 Channel 2 Channel 2 Inputs Channel 1 RTD 2 wire RTD 3 wire RTD 4 wire TC internal CJC TC internal CJC RTD 2 wire RTD 3 wire RTD 4 wire Resistance 2 wire Resistance 3 wire Resistance 4 wire TC external CJC Resistance 2 wire Resistance 3 wire Resistance 4 wire TC external CJC CONTENTS ...

Page 12: ...41 42 44 43 1 2 Outputs Channel 2 Inputs Channel 1 mV mV Channel 1 Channel 2 2 wire installation 2 wire installation TC difference or average with internal CJC TC difference or average with internal CJC TC difference or average with external CJC TC difference or average with external CJC mV difference or average mV difference or average RTD difference or average RTD difference or average HART comm...

Page 13: ...2 43 42 41 53 54 51 52 23 24 22 21 m V m A M U X 4 m A 6 3 3 5 6 3 3 5 PGA D A A D CH 1 CH 2 C P U E E P R O M Supply 4 20 mA TC mV RTD lin R wire Ex circuit only 6335D Internal CJC connectors must be ordered separately Supply HART comm HART comm Comm CONTENTS ...

Page 14: ...led in the safe area to connect the terminals of the communications interface to the pins Loop Link is not approved for communication with modules installed in hazardous Ex area Order Loop Link PRetrans 6335 44 43 42 41 51 1 2 11 12 13 14 14 24 11 21 File Product Input Output Communication Language Option 08 30 00 PRetop 5331 Date 2004 8 10 043201594 PRelectronics Analog input Analog output Serial...

Page 15: ...s A S Order HART communicator 275D 13 23 12 22 File Product Input Output Communication Language Option 08 30 00 PRetop 5331 Date 1994 8 10 943201594 PRelectronics Analog input Analog output Serial no Input type Output type 4 20mA Upscale Sensor error Pt100 DIN IEC 0 00 50 00 C 3 wire 1 00 sec Input range Connection Cold junction comp Response time Tag no PRetrans 6335 44 43 42 41 51 1 2 11 12 13 1...

Page 16: ... 2 transmitters are configured with the same number both will be excluded The transmitters must be programmed for multidrop mode with a fixed output signal of 4 mA Maximum current in the loop is therefore 60 mA The communication is either by means of a HART communicator or a HART modem The PReset PC configuration software can configure the individual transmitter for multidrop mode and provide it w...

Page 17: ...6335V109 IN 15 Appendix ATEX Installation Drawing 6335A ATEX Installation Drawing 6335D IECEx installation drawing 6335D FM Installation Drawing No 6335QF01 CSA Installation Drawing No 6335QC02 CONTENTS ...

Page 18: ...king Standards EN 60079 0 2006 EN 60079 11 2007 EN 60079 15 2005 Special conditions for safe use For use in a potentially explosive atmosphere of flammable gasses vapours or mists the transmitter shall be mounted in an enclosure providing a degree of protection of at least IP54 in accordance to EN60529 II 3 G Ex nA nL IIC T6 T5 II 3 G Ex nL IIC T6 T5 II 3 G Ex nA ic IIC T6 T5 II 3 G Ex ic IIC T6 T...

Page 19: ...umber ATEX Certificate KEMA 09ATEX 0148 Marking Standards EN 60079 0 2006 EN 60079 11 2007 EN 60079 26 2007 Installation notes The Instructions provided with the equipment shall be followed in detail to assure safe operation Non Hazardous Area Hazardous area Zone 0 1 2 II 1 G Ex ia IIC T6 T5 Terminal 41 42 43 44 Uo 9 6 VDC Io 28 mA Po 67 mW Lo 35 mH Co 3 5 μF Terminal 11 12 13 14 and 21 22 23 24 U...

Page 20: ...erial number IECEx Certificate IECEx KEM 10 0084 Marking Standards IEC60079 11 2006 IEC60079 0 2007 IEC60079 26 2006 Installation notes The Instructions provided with the equipment shall be followed in detail to assure safe operation Non Hazardous Area Hazardous area Zone 0 1 2 Ex ia IIC T5 Ga Terminal 41 42 43 44 Uo 9 6 VDC Io 28 mA Po 67 mW Lo 35 mH Co 3 5 μF Terminal 11 12 13 14 and 21 22 23 24...

Page 21: ...a or Lo Li Lcable Installation notes The Transmitter must be installed in a suitable enclosure to meet installation codes stipulated in The National Electrical Code ANSI NFPA 70 When installed in Class II locations the Transmitter shall be installed in an enclosure with a specified ingress protections of IP6X according to IEC60529 and Dust tight conduit seals must be used Equipment that is FM appr...

Page 22: ...g wiring must be less than the capacitance Ca which can be safely connected to the barrier The sum of the maximum unprotected inductance Li for each intrinsically device and the interconnecting wiring must be less than the inductance La which can be safely connected to the barrier The entity parameters Uo VOC or Vt and Io ISC or It and Ca and La for barriers are provided by the barrier manufacture...

Page 23: ...t be installed in a suitable enclosure to meet installation codes stipulated in the Canadian Electrical Code CEC Non hazardous location max 250V T6 40 to 60 deg Celcius Separate Power Supply Receiving Instrument Hazardous Locations Sécurité Intrinséque Ambient temperature limits SENSOR 1 Intrinsically safe Barrier Parameters Uo Voc 30V Io Isc 120mA Po 0 84 W CSA approved Barrier Terminal 11 14 and...

Page 24: ...rical Code CEC Non hazardous location max 250 V Hazardous Locations Sécurité Intrinséque Transmitter Power Supply built into CSA approved Receiving Instrument SENSOR 1 Ambient temperature limits T6 40 to 60 deg Celcius 6335D Transmitter Power Supply built into CSA approved Receiving Instrument SENSOR 2 Channel 2 Channel 1 41 44 54 51 14 11 21 24 Intrinsically safe Barrier Parameters Uo Voc 30V Io ...

Page 25: ...lvanic isolators for analogue and digital signals as well as HART signals A wide product range with both loop powered and universal isolators featuring linearisation inversion and scaling of output signals Isolation Interfaces for analogue and digital signals as well as HART signals between sensors I P converters frequency signals and control systems in Ex zone 0 1 2 and for some modules in zone 2...

Page 26: ...ax 45 86 37 30 85 www prelectronics fr sales prelectronics fr www prelectronics de sales prelectronics de www prelectronics es sales prelectronics es www prelectronics it sales prelectronics it www prelectronics se sales prelectronics se www prelectronics co uk sales prelectronics co uk www prelectronics com sales prelectronics com ...

Reviews: