ATEX Installation drawing
6335
For safe installation of 6335D the following must be observed. The module shall only be installed by
qualified personnel who are familiar with the national and international laws, directives and
standards that apply to this area.
Year of manufacture can be taken from the first two digits in the serial number.
ATEX Certificate KEMA 09ATEX 0148
Marking
Standards
EN 60079-0 : 2006, EN 60079-11 : 2007, EN 60079-26 : 2007
Installation notes
The Instructions provided with the equipment shall be followed in detail to assure safe
operation.
Non Hazardous Area
Hazardous area
Zone 0, 1, 2
II 1 G Ex ia IIC T6...T5
Terminal:
41,42,43,44
Uo: 9.6 VDC
Io: 28 mA
Po: 67 mW
Lo: 35 mH
Co: 3.5
μ
F
Terminal:
11,12,13,14 and
21,22,23,24
Ui: 30 VDC
Ii: 120 mA
Pi: 0.84 W
Li: 10
μ
H
Ci: 2.0nF
T5: -40
≤
Ta
≤
60ºC
T6: -40
≤
Ta
≤
40ºC
Terminal:
51,52,53,54
Uo: 9.6 VDC
Io: 28 mA
Po: 67 mW
Lo: 35 mH
Co: 3.5
μ
F
13
12
44
43
42
41
+
-
Barrier
23
22
54
53
52
51
+
-
Barrier
6335
CH2
CH1
21
24
14
11
Ex HART
Communicator
R
R
250 < R < 1100 ohm