IECEx Installation drawing
For safe installation of 6335D or 6336D the following must be observed. The module shall only be
installed by qualified personnel who are familiar with the national and international laws, directives
and standards that apply to this area.
Year of manufacture can be taken from the first two digits in the serial number.
IECEx Certificate IECEx KEM.10.0084
Marking
Standards
IEC60079-11:2006, IEC60079-0: 2007, IEC60079-26: 2006
Installation notes
The Instructions provided with the equipment shall be followed in detail to assure safe
operation.
Non Hazardous Area
Hazardous area
Zone 0, 1, 2
Ex ia IIC T5 Ga
Terminal:
41,42,43,44
Uo: 9.6 VDC
Io: 28 mA
Po: 67 mW
Lo: 35 mH
Co: 3.5
μ
F
Terminal:
11,12,13,14 and
21,22,23,24
Ui: 30 VDC
Ii: 120 mA
Pi: 0.84 W
Li: 10
μ
H
Ci: 2.0 nF
T5: -40
≤
Ta
≤
60ºC
Terminal:
51,52,53,54
Uo: 9.6 VDC
Io: 28 mA
Po: 67 mW
Lo: 35 mH
Co: 3.5
μ
F
13
12
44
43
42
41
+
-
Barrier
23
22
54
53
52
51
+
-
Barrier
6335D
6336D
CH2
CH1
21
24
14
11
Ex HART
Communicator
R
R
250 < R < 1100 ohm
CONTENTS