Version No. V1R0
7
Safety Manual
9106 HART® transparent repeater
9. failure category SIl 2 / SIl 3
10. Periodic proof test procedure
This test will detect approximately 95% of possible “du” (dangerous undetected)
failures in the module.
11. Procedures to repair or replace the product
Any failures that are detected and that compromise functional safety should be
reported to the sales department at PR electronics A/S.
Repair of the module and replacement of circuit breakers must be done by PR
electronics A/S only.
12. maintenance
No maintenance required.
Step action
1
Bypass the safety PLC or take other appropriate action to avoid a false trip
2
Connect a simulator identical to the input setup
3
Apply input value corresponding to 0/100% output range to each channel
4
Observe whether the output channel acts as expected
5
Restore the input terminals to full operation
6
Remove the bypass from the safety PLC or otherwise restore normal operation
failure category
failure rates (1/h) SIl 2
Fail Safe Detected
0.000E-0
Fail Safe Undetected
1.65E-07
Fail Dangerous Detected
1.60E-07
Fail Dangerous Undetected
4.10-08
failure category
failure rates (1/h) SIl 3
Fail Safe Detected
0.000E-0
Fail Safe Undetected
3.05E-07
Fail Dangerous Detected
3.63E-07
Fail Dangerous Undetected
1.10-08