9106QF01
LERBAKKEN 10, 8410 RØNDE DENMARK
Revision date:
2011-11-02
Version Revision
V3 R0
Prepared by:
PB
Page:
4/5
Simple Apparatus or
Intrinsic safe apparatus
with entity parameters:
Vmax (Ui)
≥
Vt (Uo)
Imax (Ii)
≥
It (Io)
Pi
≥
Pt (Po)
Ca
≥
C
cable
+ Ci
La
≥
L
cable
+ Li
9106B1A, 9106B1B
Ex input: Loop current source 1 to 2
CH1 (terminal 44)
CH2 (terminal 52)
U
o
:
28 V
I
o
:
93 mA
P
o
:
0.65 W
IIC or A,B IIB or C,E,F
IIA or D,G
C
o.
0.08
F 0.600
F 2.15
F
L
o.
3 mH
12 mH
25 mH
-20
≤
Ta
≤
+60ºC
(terminal 11,12,13,14)
(terminal 31,32,33,34)
(terminal 91,92,93,94,95)
U
m
: 253V, max 400Hz
44
43
42
41
54
53
52
51
34
33
32
31
14
13
12
11
9106
4501
91 92 93 94 95
Power
Rail
CH1
CH2
+
-
T
9106B2A, 9106B2B
Ex input: Loop current source 1 to 2
CH1 (terminal 44)
CH2 (terminal 52)
U
o
:
25.6 V
I
o
:
100 mA
P
o
:
0.64 W
IIC or A,B IIB or C,E,F IIA or D,G
C
o.
0.10
F 0.800
F 2.75
F
L
o.
2 mH
9 mH
15 mH
Hazardous Classified Location Unclassified Location or
Class I/II/III, Division 1, Group A,B,C,D,E,F,G
Hazardous Classified Location
Zone 0,1, 2 Group IIC, IIB, IIA or Class I, Division 2, Group ABCD T4
Zone 20, 21
Class I Zone 2 Group IIC T4
9106 - Product version 9106-002
36