9106 - Product version 9106-002
11
Ex barrier data:
B1x: ............................................................................... Uo = 28 V
Io = 93 mA
Po = 0.65 W
B2x: ............................................................................... Uo = 25.6 V
Io = 100 mA
Po = 0.64 W
Current output:
Signal range ............................................................... 3.5...23 mA
Load (max.) ................................................................. 20 mA / 600
Ω
/ 12 VDC
Load stability .............................................................
≤
0.01% of span / 100
Ω
Current limit ...............................................................
≤
28 mA
Passive 2-wire output installation:
Max. external 2-wire supply ............................... 26 VDC
Max. load resistance [
Ω
] ....................................... (V
supply
- 3.5) / 0.023 A
Effect of external 2-wire supply
voltage variation ...................................................... < 0.005% of span / V
*of span = normal measurement range 4...20 mA
Status relay output terminal 33-34:
Relay function ........................................................... N.C.
Programmable low setpoint ................................ 0...29.9 mA
Programmable high setpoint ............................... 0...29.9 mA
Hysteresis for setpoints ....................................... 0.1 mA
Max. voltage .............................................................. 110 VDC / 125 VAC
Max. current ............................................................... 0.3 ADC / 0.5 AAC
Max. voltage - hazardous installation ............. 32 VDC / 32 VAC
Max. current - hazardous installation .............. 1 ADC / 0.5 AAC