OPERATOR PARAMETERS
Section 3
Parameter Description
Settings
(Default Value)
Table 3.1
Yes
No
(Default : No)
The Table 3.1 below described the Operator Parameters in detail.
Figure 3.1
°C
25.0
25.0
TEMP HIGH
SP
or
Next Parameter
HI DEVIATION >>
2.0
LO DEVIATION >>
2.0
Desired Parameter
LO DEVIATION >>
5.0
Desired Value
Press UP/DOWN Keys
to adjust Parameter Value
Press ENTER Key
to store the New Value
& to move to Next Parameter
ENTER PASSWORD >>
0
CTRL SET VALUE >>
25.0
RUN Mode
Main Screen
Default Password
for Operator Parameters
First Parameter
Press SET-UP Key
for Password Entry
Press ENTER Key
To open Operator
Parameter List
Press & Release
ENTER Key until Desired
Parameter appears
(Available only if Timer is Enabled)
These two commands are mutually exclusive.
Set to Yes to start Timer, if not already started.
Set to Yes to abort a running timer.
TIME START COMMAND
>>
TIME ABORT COMMAND >>
0.01 to 249.59
(HH:MM)
(Default : 0.10)
TIME INTERVAL (H:M) >>
(Available only if Timer is Enabled)
The set time value for the timer in Hours : Minutes.
The Operator Parameters are accessible under PASSWORD 0. The list includes parameters for adjusting Control Setpoint,
Alarm Setpoints & Zero-offset. If Timer is enabled then Time Interval value & Timer Start / Abort commands are also available.
The Figure 3.1 shows how to access Operator Parameters. The Example illustrates changing the Low Deviation alarm value
from 2.0 to 5.0. (The Example is shown with Timer disabled).