
19
Zenex Plus
User Manual
FACTORY
DOOR OPEN
Parameter Description
Settings
(Default Value)
Close : Door Open
The Door position is considered
if the switch is CLOSE.
Open
Open : Door Open
The Door position is considered
if the switch is OPEN.
Open
SWITCH LOGIC >>
(Default : CLOSE : DOOR OPEN)
CLOSE : DOOR OPEN
OPEN : DOOR OPEN
This parameter sets a timer. From the time the door is opened, the
timer begins counting down. If the door is not closed before the
timer reaches 0, the
Door Open
alarm is activated.
DOOR ALRM DLY (SEC) >>
(Default : 60 Sec)
0 to 1000 Sec
(Default : NO)
YES
NO
Set to ‘Yes’ if
is mounted for detecting
Switch
door
Open / Close
position.
ENABLE >>
FACTORY
PASSWORD
Parameter Description
Settings
(Default Value)
CHANGE PASSWORD >>
The Controller is shipped from the factory with a default password
(321) for accessing the parameters reserved for the
equipment
manufacturer. owever, if required the password can be changed
H
by setting the new value for this parameter.
(The new password replaces the old password. hat is, the old
T
password is no longer valid. it is user’s responsibility to memorize
the password.)
(Default : 321)
2000 to 2999
FACTORY
FACTORY DEFAULT
Parameter Description
Settings
(Default Value)
Set to ‘Yes’ to set all the parameter values to their Default alues.
V
SET TO DEFAULT >>
(Default : NO)
YES
NO