ELECTRICAL CONNECTION
The Electrical Connection Diagram is shown on the Top Side of the enclosure. The diagram shows the terminals viewed from
the REAR SIDE with the front label upright. The terminal numbers are also embossed on the rear side of the enclosure. Refer
figure 12.1.
Figure 12.1
DIGITAL INPUT FOR BATCH START COMMAND
Connect a remote potential-free contact closure switch for the purpose of issuing the Batch -
Recording START command. An ‘OPEN’ to ‘CLOSE’ change over of the contacts initiates time
based batch recording. Once the recording starts, the change in the contact status has no effect.
Figure 12.2
2
1
Batch Start
Switch
DIGITAL INPUT FOR ALARM ACKNOWLEDGE
Connect a remote potential-free contact closure switch for the purpose of issuing Alarm
Acknowledgment. An ‘OPEN’ to ‘CLOSE’ change over of the contacts acknowledges the alarm and
mutes the alarm relay(s).
Figure 12.3
4
3
Switch
Alarm ACK
ALARM-1 RELAY OUTPUT
This relay output status is determined by logically ORing the Alarm-1 status of all the devices.
Potential-free Relay changeover contacts NO (Normally Open) and C (Common) rated 2A/240
VAC (resistive load) are provided as Relay output.
Figure 12.4
Alarm-1
15 16
C
NO
RLY
User Manual
UniRec
23
Section 12