Chapter 4 Installation and commissioning
23
Ch
ap
ter
4
4-5.Commissioning
Select control mode
setting F0.00)
F0.00=?
Select command
source(Set F0.11)
Select suitable frequency
source(Set F0.03)
Select motor start-up
mode(Set F3.00)
Select appropriate ac/deceleration
time(Set F0.13,F0.14)
Select motor stop
mode(Set F3.07)
Start motor to run,observe the
phenomenon,if abnormal,please
refer to the trouble shooting
Achieve the required control
effect?
Correctly motor
parameters(Set b0.00-b0.05
Select appropriate ac/deceleration
time(Set F0.13,F0.14)
Motor parameter
self-learning(Set b0.27)
2 V/F control
0 Vector control
W/O PG
YES
NO
Commissioning
Commissioning
Figure 4-7
●
Firstly confirm that AC input power supply voltage shall be within inverter rated
input voltage range before connecting power supply to the inverter.
●
Connect power supply to the R, S and T terminals of the inverter. or solar power to
the R, T input terminals of the inverter.
●
Select the appropriate operation control method.