Chapter 5 Function parameter
30
Ch
ap
ter
5
DIx, the motor direction signal is generated by DIy status
To stop, you must disconnect DIn terminal signals Of which, DIx, DIy and DIn are the multi-
function input terminals of DI1 to DI10, DIx is for active pulse, DIy and DIn are for active level.
DIx
DIn
DIy
COM
Digital common
terminals
SB2
SB1
K
K
0
1
Three-wire operation
control
Reverse run
REV
Forward run FWD
Command
REV
FWD
Three-wire control model 2
Of which:SB1:stop button SB2:Run button
F1.12 AIC1 Minimum input
0.00V~F1.14
0.00V
☆
F1.13 F1.12 corresponding setting -100%~+100.0%
0.0%
☆
F1.14 AIC1 Maximum input
F1.12~+100%
10.00V
☆
F1.15 F1.14 corresponding setting -100%~+100.0%
100.0%
☆
F1.16 AIC2 Minimum input
0.00V~F1.14
0.00V
☆
F1.17 F1.16 corresponding setting -100%~+100.0%
0.0%
☆
F1.18 AIC2 Maximum input
F1.12~+100%
10.00V
☆
F1.19 F1.18 corresponding setting -100%~+100.0%
100.0%
☆
F1.35
DI Terminal Mode Selection
1
Unit digit DI1 Terminal active state set
00001
★
High level active
0
Low level active
1
Ten digit
DI2 Terminal active state set(0-
1,same as the units digit)
Hundreds
digit
DI3 Terminal active state set(0-
1,same as the units digit)
Thousand
digit
DI4 Terminal active state set(0-
1,same as the units digit)
Ten
thousands
digit
DI5 Terminal active state set(0-
1,same as the units digit)
F1.37 DI1 delay time
0.0s~3600.0s
0.0s
★
F1.38 DI2 delay time
0.0s~3600.0s
0.0s
★
F1.39 DI3 delay time
0.0s~3600.0s
0.0s
★
F1.40
Define the input terminal
repeat
0:unrepeatable
;
1:repeatable
0
★
5-1-4.F2 Output terminal group
Code
Description/Keyboard display
Setting range
Factory
setting
Change
Limit
F2.00 SPB terminal output selection
High speed pulse output
0
0
☆
Switching output
1
SPB terminals are programmable multiplex terminal can be used as high-speed pulse output
terminal,it can also be used as open collector output terminal.