Chapter 5 Function parameter
33
Ch
ap
ter
5
Analog Output DA1 and DA2 output range is 0V ~ 10V, or 0mA ~ 20mA. Pulse output or
analog output range, with the corresponding scaling function relationship in the following table:
Setting
value
Functions
Description
0
Running frequency
0~Max. output frequency
1
Set frequency
0~Max. output frequency
2
Output current
0~2 times the motor rated current
4
Output power
0~2 times rated power
5
Output voltage
0~1.2 times inverter rated voltage
6
High speed pulse input
0.01kHz~100.00kHz
7
Anolog AI1
0V~10V
8
AnologAI2
0V~10V(or 0~20mA)
12
Coummunication set
0.0%~100.0%
13
Motor speed
0~Max. output frequency correspondent speed
14
Output current
0.0A~100.0A(Inverter power
≦
55kW)
;
0.0A~1000.0A(Inverter power>55kW)
15
DC bus voltage
0.0V~1000.0V
17
Frequency source main set
0~Max. output frequency
F2.09
Maximum frequency of high-
speed pulse
0.01kHz~100.00kHz
50.00kHz
☆
When the SPB terminal as a pulse output, the function code is used to select the maximum
output pulse frequency value.
F2.10 SPB output delay
0.0s~3600.0s
0.0s
☆
F2.11 Relay 1 output delay time
0.0s~3600.0s
0.0s
☆
F2.13 SPA output delay time
0.0s~3600.0s
0.0s
☆
F2.14 Relay 2 output delay time
0.0s~3600.0s
0.0s
☆
Set the output terminal SPA, SPB, relay 1, relay 2, delay time of changing from the state
produced to the actual output differentiated.
F2.15
DO terminal active
status selection
Units digit SPB switching active status selection
00000
☆
Positive
0
Negative
1
Tens digit
Relay 1 active setting (0 to 1,
as defined in units digit)
Hundreds digit Reserve
Thousands
digit
SPA Terminal active state
settings (0 to 1, as defined in
units digit)
Tens thousand
digit
Relay 2 active setting (0 to 1,
as defined in units digit)
Define the output terminal SPA, SPB, relay 1, relay 2 output logic.
0: positive, digital output terminal and the corresponding public terminal connectivity to the
active state, disconnecting is inactive state;
1: negative, digital output terminal and the corresponding public terminal connectivity to the
inactive state, disconnecting is active state.
Summary of Contents for PI500-S 004G1