![Powerware 5125 Tower User Manual Download Page 25](http://html1.mh-extra.com/html/powerware/5125-tower/5125-tower_user-manual_1592066025.webp)
22
Table 5. Technical Specifications
Operating Frequency
50/60 Hz, auto-sensing
Frequency Range
46-65 Hz
Noise Filtering
MOVs and line filter for normal and common mode noise
Regulation (Normal Mode)
-10% to +6% of nominal voltage
Regulation (Battery Mode)
Nominal output v5%
Voltage Waveform
Sine wave
Table 6. Environment and Safety
Operating Temperature
10
o
C to 40
o
C (Optimal Battery Performance 25
o
C)
Storage Temperature
0
o
C to 25
o
C
Transit Temperature
-25
o
C to 55
o
C
Relative Humidity
5-95% non-condensing
Operating Altitude
Up to 3,000 metres above sea level
Transit Altitude
Up to 15,000 metres above sea level
Audible Noise
Less than 40dBA Normal mode, typical load,
Less than 55dBA Battery Mode
Surge Suppression
ANSI C62.41 Category B (formerly IEEE 587), IEC 61000-4-6
Safety Conformance
UL 1778, UL 497A (data line only), CAN/CSA C22.2, No. 107.1,
EN 50091-1-1 and IEC 60950, AS/NZS60950, EN50091-1
Agency Markings
C-Tick
EMC
EN 50091-2, AS/NZS 62040.2, AS/NZS61000.3.2