IT
Akku
Zeigt den Ladungszustand des Akkus in 0-25%, 26-50%, 51-75%,
und 76-100% an.
Zeigt einen Akkudefekt an.
Zeigt einen niedrigen Ladezustand und Spannung des Akkus an.
Eingangs- & Akkuspannung
Zeigt die Eingangsspannung oder -frequenz oder die
Akkuspannung an
.
Vac: Eingangsspannung, Vdc: Akkuspannung, Hz: Eingangsfrequenz
3-3. Akustischer Alarm
Description
Buzzer status
Muted
UPS status
Bypassmodus
Ertönt alle 2 Minuten
Ja
Akkumodus
Ertönt alle 4 Sekunden
Fehler
Kontinuierlicher Ton
Warnungen
Überlastung
Ertönt zweimal jede Sekunde
Nein
Andere
Ertönt jede Sekunde
3-4. Single UPS Operation
1. Turn on the UPS with utility power supply (in AC mode)
1) After power supply is connected correctly, set the breaker of the battery pack at “ON” position (the
step only available for long-run model). Then set the line input breaker at “ON” position(for dual
input unit, also set the bypass input breaker at “ON”). At this time the fan is running and the UPS
enter to power on mode for initialization, several seconds later, UPS operates in Bypass mode and
supplies power to the loads via the bypass.
NOTE:
When UPS is in Bypass mode, the output voltage will directly power from utility after you
switch on the input breaker. In Bypass mode, the load is not protected by UPS. To protect your
precious devices, you should turn on the UPS. Refer to next step.
2) Press and hold the “ON” button for 0.5s to turn on the UPS and the buzzer will beep once.
3) A few seconds later, the UPS will enter to AC mode. If the utility power is abnormal, the UPS will
operate in Battery mode without interruption.
NOTE:
When the UPS is running out battery, it will shut down automatically at Battery mode. When the
utility power is restored, the UPS will auto restart in AC mode.
2. Turn on the UPS without utility power supply (in Battery mode)
1) Make sure that the breaker of the battery pack is at “ON” position (only for long-run model).
2) Press the “ON” button to set up the power supply for the UPS, UPS will enter to power on mode.
After initialization UPS will enter to No Output mode, then Press and hold the “ON” button for 0.5s
to turn on the UPS, and the buzzer will beep once.
3) A few seconds later, the UPS will be turned on and enter to Battery mode.
Summary of Contents for 10000
Page 2: ......