15: Inverter A voltage adjustment
Interface
Setting
Parameter 2:
you may choose
Add
or
Sub
to adjust inverter A
voltage.
Parameter 3:
the voltage range is from 0V to 9.9V and the
default value is 0V.
16: Inverter B voltage adjustment
Interface
Setting
Parameter 2:
you may choose
Add
or
Sub
to adjust inverter B
voltage*.
Parameter 3:
the voltage range is from 0V to 9.9V and the
default value is 0V.
*It will display number 1 under
or
to represent
inverter B voltage.
17: Inverter C voltage adjustment
Interface
Setting
Parameter 2:
you may choose
Add
or
Sub
to adjust inverter C
voltage*.
Parameter 3:
the voltage range is from 0V to 9.9V, the default
value is 0V.
*It will display number 2 under
or
to represent
inverter C voltage.
18: Output A voltage calibration
Interface
Setting
Parameter 2:
it always shows
OP.V
as output voltage.
Parameter 3:
it shows the internal measurement value of the
output A voltage, and you can calibrate it by pressing
Up
or
Down
according to the measurement from an external voltage meter.
The calibration result will be effective by pressing
Enter
. The
calibration range is limited /-9V. This function is normally
used for parallel operation.
19: Output B voltage calibration
Interface
Setting
Parameter 2:
it always shows
OP.V
as output voltage*.
Parameter 3:
it shows the internal measurement value of the
output B voltage, and you can calibrate it by pressing
Up
or
Down
according to the measurement from an external voltage meter.
The calibration result will be effective by pressing
Enter
. The
calibration range is limited /-9V. This function is normally
used for parallel operation.
*It will display number 1 under
to represent the output B
voltage.
20: Output C voltage calibration