IT
1)
Press the “OFF” key twice and each time should be lasted for more than 0.5s. Then, the UPS will
enter into bypass mode or no output mode without output.
2)
Turn off the output breaker of this unit, and then turn off the input breaker of this unit.
3)
After it shuts down, you can turn off the battery breaker (for long-run model) and remove the
parallel and share current cables. And then remove the unit from the parallel system.
Second method:
1)
If the bypass is abnormal, you can not remove the UPS without interruption. You must cut off the
load and shut down the system first.
2)
Make sure the bypass setting is enabled in each UPS and then turn off the running system. All UPSs
will transfer to Bypass mode. Remove all the maintenance bypass covers and set the maintenance
switches from “UPS” to “BPS”. Turn off all the input breakers and battery breakers in parallel system.
3)
Turn off the output breaker and remove the parallel cable and share current cable of the UPS which
you want to remove. Then, remove it from parallel system.
4)
Turn on the input breaker of the remaining UPS and the system will transfer to Bypass mode.
Set
the maintenance switches from “BPS” to “UPS and put the maintenance bypass covers back.
5)
Turn on the remaining UPS according to the previous section.
Warning:
(Only for the parallel system)
● Before turning on the parallel system to activate inverter, make sure that all
unit’s maintenance switch
at the same position.
● When
parallel system is turned on to work through inverter, please do not operate the maintenance
switch of any unit.
3-6. LCD-Display Index der Formulierungen
Abkürzung
Anzeige
Bedeutung
ENA
Aktivieren
DIS
Deaktivieren
ATO
Auto
BAT
Akku
NCF
Normal Modus
CF
Konverter-Modus
SUB
Subtract
ADD
Hintufugen
ON
An
OFF
Aus
FBD
Nicht erlaubt
OPN
Erlaubt
RES
Reserviert
N.L
Neutral Leitungsverlust
CHE
Prüfen
Summary of Contents for 10000
Page 2: ......