2.4 WIRE
SIZING
Care must be taken to properly size all conductors for the input and output of the power
supply. Table 2-5 below gives
minimum
recommended wire size for the input. This
table is derived from the National Electrical Code and is for reference only. Local laws
and conditions may have different requirements. The table is for copper wire only.
Table 2-5
Minimum Wire SizeTable
SIZE
60 °C
75 °C
85 °C
90 °C
TYPES
TYPES
TYPES
TYPES
AWG
MCM
RUW, T, TW,
UF
FEPW, RH,
RHW, RUH,
THW, THWN,
XHHW, USE,
ZW
V, MI
TA, TBS, SA,
AVB, SIS, FEP,
FEPB, RHH,
THHN, XHHW
14
20
20
25
25
12
25
25
30
30
10
30
35
40
40
8
40
50
55
55
6
55
65
70
75
4
70
85
95
95
3
85
100
110
110
2
95
115
125
130
1
110
130
145
150
0
125
150
165
170
00
145
175
190
195
000
165
200
215
225
0000
195
230
250
260
TEMPERATURE RATING OF COPPER CONDUCTOR
CURRENT RATING
For higher ratings wires can be paralleled or refer to the National Electrical Code.
Refer to Table 2-6 for AC input current requirements.
Table 2-6
Maximum AC Current Ratings
Input Line Current
Input V
3.3 kW
6.6 kW
10 kW
13.3 kW
16.6 kW
20 kW
Unit of
Measure
200-240
VAC
15 29 44 57 72 87
360-440
VAC
10 19 28 37 46 56
480
VAC
9 18 27 35 44 53
Amps AC
per
phase
M550001-01
2-5
Summary of Contents for D3 Series
Page 2: ......
Page 3: ......
Page 4: ......
Page 28: ...This page intentionally left blank M550001 01 2 12 ...
Page 44: ...This page intentionally left blank M550001 01 3 16 ...
Page 59: ...Figure 4 4 P83 P86 Internal Layout M550001 01 4 15 ...
Page 60: ...Figure 4 5 P83 P86 Converter Card M550001 01 4 16 ...
Page 61: ...Figure 4 6 P63 P66 Converter Card M550001 01 4 17 ...
Page 62: ...This page intentionally left blank M550001 01 4 18 ...