3.5.5. UPS Default Settings and their alternatives
3.5.5.1.
Make sure the UPS is not “On”. Press the On
and scroll
down
keys simultaneously
for approximately three seconds.
The buzzer will sound twice, and the LCD will display figure Q1,
indicating that the UPS is in setting mode.
3.5.5.2. To scroll through the options refer to section 3.5.4.2.
3.5.5.3. Except for Buzzer (figures Q1 and Q2) and Self-test (figures R1
and R2) all of the other default settings may be changed by
pressing the scroll up
key.
3.5.5.4. Figures S1 and S2 indicate the bypass input acceptable window.
It can be 184-260 VAC or 195-260 VAC.
3.5.5.5. Figure T indicates the bypass frequency window of the Inverter
Output. The acceptable setting values are ±3 Hz and ±1 Hz.
3.5.5.6. Figure U indicates the acceptable Inverter Output Voltage.
Possible values are 200, 208, 220, 230, or 240 VAC.
3.5.5.7. Figures V1, V2, V3 and V4 indicate the operation modes of the
UPS. Possible values are Online, Eco (Economical) mode, fixed
50 Hz Output, and fixed 60 Hz Output.
3.5.5.8. Figure W indicates the adjustment of the Inverter Output, which
may be set to 0%, +1%, -1%, +2%, -2%, +3%, or -3%.
3.5.5.9. Figure X indicates the position of the UPS when the UPS is in
Parallel mode. Possible positions are 1, 2, 3, and 4. The position
must be 1 if the UPS is not in Parallel mode.
3.5.5.10. Figure Y indicates the parallel function status
. “P 01” indicates
that the parallel function is disabled, and
“P 02” indicates that the
parallel function is enabled.
3.5.5.11. After changing settings you
must scroll to the “End” screen
(figure Z) and then press the enter
key to save all of your
changes. Then the LCD will display figure AA to indicate
completion of the setting changes. To cancel your changes rather
than save them press and hold the
“OFF” key
for five
seconds. The LCD displays figure AA directly, which indicates
that your changes were canceled.
Z
Summary of Contents for 10000
Page 1: ...Parallel Redundancy On Line UPS User Manual 4 5 6 8 10 15 and 20 kVA ...
Page 14: ...13 2 3 2 Rear Panel Also available for Rack ...
Page 22: ...21 ...
Page 29: ...28 buzzer Off ...
Page 32: ...31 The UPS is operating in CVCF 50 Hz mode ...
Page 44: ...43 1 2 3 6 6 Interface Card Installation ...
Page 46: ...45 ...
Page 52: ...51 192321132115000 ...