22
3.5.
Installation and Operation
3.5.1. Start Up in Normal Mode
3.5.1.1. Open the terminal block cover on the rear panel. (Refer to 2.3.2.)
Before starting the installation make sure the grounding is
connected properly.
3.5.1.2. Make sure the utility breaker and the
UPS’ Utility breaker and
Bypass breaker are in the
“Off” position.
3.5.1.3. Make sure the utility voltage matches the input voltage window of
the UPS.
3.5.1.4. Connect the utility separately to the terminal blocks of the UPS
’
Utility and Bypass inputs. Switch on the power breaker of the
distribution panel and the breakers of the UPS
’ Utility and Bypass
inputs. Then the UPS will start up. Green LEDs
and
show that the Utility and Bypass inputs are normal. UPSs with
parallel function enabled will display first figure A1, then figure A2,
and then figure B. Otherwise the LCD will display figure A1
directly followed by figure B.
A1.
A2.
B.