20
●
Use mounting cable ties to fix cables.
6. Please refer to the specifications of input current, output current and
recommended conductors listed below.
a. AC input and output (minimum 75
C copper wire)
b. Battery input
Model
Maximum Current
Conductor Section
Torque force
4.5KVA(Tower/RT)
25 A
AWG
#
10
17.7/11 lb-in
6KVA(Tower/RT)
33 A
AWG
#
8
17.7/11 lb-in
8KVA
43.4 A
AWG
#
8
23 lb-in
10KVA
54.3 A
AWG
#
6
23 lb-in
15KVA
30.2 A/83.3A(In/Out)
AWG
#
8/ #4
20KVA
39.85 A/111A(In/Out)
AWG
#
8/ #4
Model
Maximum Current
Conductor Section
4.5KVA
19 A
AWG
#
10
6KVA
25 A
AWG
#
10
8KVA
33 A
AWG
#
10
10KVA
41 A
AWG
#
10
15KVA/20KVA
62.5A/83 A
AWG
#
6/ AWG
#
4
External Battery
External Charger
T1
Tower model
6KRT model
6000C model