RED00202(R2) MANUAL

Connections

Clamping Yoke Connector Specifications 

Input / Output connections 

Signal connection plug 

Tightening torque min. – max. 

1,2 – 2,2Nm (blade 1,0x5,5 DIN5264 ) 

0,4 – 0,5Nm (blade 0,6x3,5 PH1 PZ1) 

Touch-safe protection acc. to DIN VDE 0470 

IP20 plugged/ IP10 unplugged 

Not applicable 

Clamping range, min. – max. 

0,5 – 16mm² / AWG26 – AWG6 

0,2 – 4,0mm² / AWG26 – AWG12 

Solid, H05(07) V-U min. – max. 

0,5 – 16mm² 

0,2 – 4,0mm² 

Stranded, H05(07) V-U min. – max. 

6 – 16mm² 

Not applicable 

Flexible, H05(07) V-U min. – max. 

0,5 – 16mm² 

0,2 – 4,0mm² 

w. plastic collar ferrule, DIN 46228 pt 4 min. – max.

2,5 – 10mm² 

0,2 – 2,5mm² 

w. wire end ferrule, DIN 46228 pt 1, min. – max.

2,5 – 10mm² 

0,2 – 4,0mm² 

Plug gauge in accordance with EN 60999 a x b; ø 

5,4 x 5,1mm; 5,3mm 

2,8 x 2,4mm; 2,5mm 

Pitch (P) 

10,16mm 

7,50mm 

Wire Stripping Length (fine wired) 

Nominal Cross Section 

Wire End Ferrule 

Stripping Length 

Wire End Ferrule 

Stripping Length 

0,25mm² 

H0,25/5 

5mm 

H0,25/10 HBL 

8mm 

0,5mm² 

H0,5/6 

6mm 

H0,5/12 OR 

8mm 

1,0mm² 

H1,0/6 

6mm 

H1,0/12 GE 

8mm 

2,5mm² 

H2,5/12 

12mm 

H2,5/19D BL 

14mm 

4,0mm² 

H4,0/12 

12mm 

H4,0/20 GDR 

14mm 

6,0mm² 

H6,0/20 

12mm 

H6,0/20 SW 

14mm 

10,0mm² 

H10,0/12 

12mm 

H10,0/22 EB 

15mm 

The length of ferrules is to be chosen depending on the rated voltage. The outside diameter of the plastic collar should not be larger than 
the pitch (P) 

Ordering Information

Ordering Codes 

Product Code 

Volt 

Power 

Information 

Article Number 

RED00202A(R2) 

0 – 28Vdc 

1000W 

below 12Vdc is the DC-OK relay without function 

3041049001CA 

RED00202B(R2) 

36 – 60Vdc 

1000W 

3041049002CA 

RED00202C(R2) 

90 – 125Vdc 

1000W 

3041049003CA 

Electrical Safety (Factory-Test / Field-Test Owner) 

 
 
 

  
 

Type and factory test are the manufacturer. While repeating damage can 
happen to the power supply unit. For the field test (owner) follow the below instruction:

 

a)

Use suitable test equipment, raising the voltage slowly.

b)

Use only test voltages of 50/60Hz. The outputs are unearthed and
therefore they have no resistance to GND/PE.

c)

If the residual voltage is 

60Vdc, observe the safety standards.

Use only specially insulated screwdriver to trim the Ua/Ia.

A

1)

 

Type Test 

60s 

500Vac 

500Vdc 

Factory Test 

5s 

500Vac 

500Vdc

 

Field Test 

2s 

500Vac 

500Vdc

 

Cut-off current setting  >1mA

>1mA

1)

60Vdc = 1500Vdc

[email protected]

www.powersolve.co.uk

020321

Summary of Contents for RED00202A

Page 1: ...protected Monitoring relay floating Low voltage drop Screw terminals 16mm2 EN62368 1 Schottky barrier decoupling diodes Efficiency 97 Adjustable drop out voltage detection 20 C 70 C ambient temperature IP20 metal housing Models Voltage RED00202A R2 0 28Vdc RED02020B R2 36 60Vdc RED00202C R2 90 125Vdc sales powersolve co uk www powersolve co uk 020321 ...

Page 2: ...wer Good Relay Change over contact Relay contact load 48Vdc 500mA max Relay contact separation Protective electrical insulation 60Vdc Cooling Natural convection Ambient temperature 20 C 70 C Storage temperature 40 C 85 C Environment Humidity 95 non condensing 25 C climate class 3k3 pollution degree 2 ROHS 2011 65 EU EU 2015 863 REACH EG No 1907 2006 EMI EN55032 class B EN61000 6 3 EMS EN61000 6 2 ...

Page 3: ...p between DC input and DC output is between 500mV and 700mV see table Technical Data Current voltage graph Voltage control specification The change over contact of the control relay is at the left position when the input voltage V1in and V2in operate between Vu and Vo The LED of each input lights green The relay contact changes to the right position when the input voltages are either smaller Vu or...

Page 4: ...ED00202 Stable metal aluminium housing IP20 To allow adequate convection a free air space of 50mm top bottom and 10mm sidewalls is required and for active devices 15mm space from the sidewalls For proper air convection it is necessary to install the RED One can use the DIN Rail installation equipped standard with our patented 35mm DIN Rail bracket according to EN60715 It is easy to mount dismount ...

Page 5: ... H4 0 12 12mm H4 0 20 GDR 14mm 6 0mm H6 0 20 12mm H6 0 20 SW 14mm 10 0mm H10 0 12 12mm H10 0 22 EB 15mm The length of ferrules is to be chosen depending on the rated voltage The outside diameter of the plastic collar should not be larger than the pitch P Ordering Information Ordering Codes Product Code Volt Power Information Article Number RED00202A R2 0 28Vdc 1000W below 12Vdc is the DC OK relay ...

Page 6: ...ng bolts or operation outside the specified herein specification or in an unsuitable environment has the immediate loss of warranty to follow We disclaim any responsibility for any resulting damage to persons or things Warning Non compliance these warnings can result in fire and serious injury or death 1 Allow neat and professional cabling 2 Never open nor try to repair the unit Inside are dangero...

Reviews: