RED00202(R2) MANUAL
Connections
Clamping Yoke Connector Specifications
Input / Output connections
Signal connection plug
Tightening torque min. – max.
1,2 – 2,2Nm (blade 1,0x5,5 DIN5264 )
0,4 – 0,5Nm (blade 0,6x3,5 PH1 PZ1)
Touch-safe protection acc. to DIN VDE 0470
IP20 plugged/ IP10 unplugged
Not applicable
Clamping range, min. – max.
0,5 – 16mm² / AWG26 – AWG6
0,2 – 4,0mm² / AWG26 – AWG12
Solid, H05(07) V-U min. – max.
0,5 – 16mm²
0,2 – 4,0mm²
Stranded, H05(07) V-U min. – max.
6 – 16mm²
Not applicable
Flexible, H05(07) V-U min. – max.
0,5 – 16mm²
0,2 – 4,0mm²
w. plastic collar ferrule, DIN 46228 pt 4 min. – max.
2,5 – 10mm²
0,2 – 2,5mm²
w. wire end ferrule, DIN 46228 pt 1, min. – max.
2,5 – 10mm²
0,2 – 4,0mm²
Plug gauge in accordance with EN 60999 a x b; ø
5,4 x 5,1mm; 5,3mm
2,8 x 2,4mm; 2,5mm
Pitch (P)
10,16mm
7,50mm
Wire Stripping Length (fine wired)
Nominal Cross Section
Wire End Ferrule
Stripping Length
Wire End Ferrule
Stripping Length
0,25mm²
H0,25/5
5mm
H0,25/10 HBL
8mm
0,5mm²
H0,5/6
6mm
H0,5/12 OR
8mm
1,0mm²
H1,0/6
6mm
H1,0/12 GE
8mm
2,5mm²
H2,5/12
12mm
H2,5/19D BL
14mm
4,0mm²
H4,0/12
12mm
H4,0/20 GDR
14mm
6,0mm²
H6,0/20
12mm
H6,0/20 SW
14mm
10,0mm²
H10,0/12
12mm
H10,0/22 EB
15mm
The length of ferrules is to be chosen depending on the rated voltage. The outside diameter of the plastic collar should not be larger than
the pitch (P)
Ordering Information
Ordering Codes
Product Code
Volt
Power
Information
Article Number
RED00202A(R2)
0 – 28Vdc
1000W
below 12Vdc is the DC-OK relay without function
3041049001CA
RED00202B(R2)
36 – 60Vdc
1000W
3041049002CA
RED00202C(R2)
90 – 125Vdc
1000W
3041049003CA
Electrical Safety (Factory-Test / Field-Test Owner)
Type and factory test are the manufacturer. While repeating damage can
happen to the power supply unit. For the field test (owner) follow the below instruction:
a)
Use suitable test equipment, raising the voltage slowly.
b)
Use only test voltages of 50/60Hz. The outputs are unearthed and
therefore they have no resistance to GND/PE.
c)
If the residual voltage is
≥
60Vdc, observe the safety standards.
Use only specially insulated screwdriver to trim the Ua/Ia.
T
A
1)
B
Type Test
60s
500Vac
500Vdc
Factory Test
5s
500Vac
500Vdc
Field Test
2s
500Vac
500Vdc
Cut-off current setting >1mA
>1mA
1)
≥
60Vdc = 1500Vdc